![LS ELECTRIC H100 0008-2(PLUS) Manual Download Page 233](http://html1.mh-extra.com/html/ls-electric/h100-0008-2-plus/h100-0008-2-plus_manual_1943796233.webp)
Applying Drives to Single-
phase Input Application
207
7.3 Input Frequency and Voltage Tolerance
For single-phase input AC voltage, products with 90 kW or less are within -5% to
+ 10% of 240/480 Vac.
Products with 110 kW or more are in the range of -5% to
+ 10% of 380/500 Vac.
Standard product with three-phase voltage input has an
allowable range of
-
1
5
% to
+
1
0
%. Therefore, a stricter input voltage tolerance of
-5
to
+10
% applies when using the drive with a single-phase supply. The average bus
voltage with single-phase input is lower than the equivalent of a three-phase input.
Therefore, the maximum output voltage (motor voltage) will be lower with a single-phase
input. The minimum input voltage must be no less than 228Vac for 240 volt models and
456Vac for 480 volt models, to ensure motor voltage production of 207Vac and 415Vac,
respectively.
Thus, if full motor torque must be developed near base speed (full power) it will be
necessary to maintain a rigid incoming line voltage so that adequate motor voltage can be
produced. Operating a motor at reduced speed (reduced power), or using a motor with a
base voltage that is lower than the incoming AC supply rating (ex. 208Vac motor with a
240Vac supply), will also minimize the effect of voltage deprivation. ( 240VAC Input
208V motor, 480VAC Input
400V motor )
7.4 Wiring
Please connect single-phase input to R(L1) and T(L3).
Figure-3 Terminal Wiring Diagram
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...