![LS ELECTRIC H100 0008-2(PLUS) Manual Download Page 215](http://html1.mh-extra.com/html/ls-electric/h100-0008-2-plus/h100-0008-2-plus_manual_1943796215.webp)
Technical Specification
189
Products(kW)
AC Input Fuse
AC reactor
DC Reactor
Current
(A)
Voltage
(V)
Inductance
(mH)
Current
(A)
Inductance
(mH)
Current
(A)
15
63
0.61
33
1.42
33
18.5 70
0.48
43
0.98
42
22
100
0.40
51
0.88
50
30
125
0.29
69
0.59
68
37
0.29
69
Built-In
45
160
0.24
85
55
200
0.20
100
75
250
0.15
134
90
350
0.13
160
110
350
0.1
217
132
400
0.08
257
160
450
0.07
318
185
550
0.06
362
220
630
0.05
423
250
700
0.05
474
315
800
0.04
604
355
1000
0.03
673
400
1100
0.03
759
500
1250
0.03
948
Use Class H or RK5 UL Listed Input Fuse and UL Listed Breaker Only. See the table above for
the Voltage and Current rating of the fuse and the breaker.
Attention
Utiliser UNIQUEMENT des fusibles d’entrée homologués de Classe H ou RK5 UL et des
disjoncteurs UL . Se reporter au tableau ci-dessus pour la tension et le courant nominal des
fusibless et des disjoncteurs.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...