MultiController E 0-100%
LS Control A/S
Side 9
D6 (Only available if MultiController is purchased as model Regulate).
Choose if MultiController should
operate as a controller or manual (0-100%) regulator. If controlling (model Regulate) is chosen please refer to
manual for MultiControllerE Regulate, which may be downloaded from www.lscontrol.dk.
2.10
Service Menu (E-Menu)
In the service menu the advanced settings of the controller are found. Hence these settings are vital and erroneous
adjustments may ruin the function of the controller this menu is by default password protected.
Password is 5550
Below Settings may be altered in the service menu:
E1:
Model Choice (functionality choice).
Set if controller output signal is to function as ON/OFF, Stepless Percentage (0-100%), or 4-step.
E2:
Minimum Output Voltage.
If the connected equipment is unable to regulate from 0V, the minimum voltage of the output signal (Vout1) may be
adjusted in this menu point.
E3:
Maximum Output Voltage.
If the connected equipment is unable to regulate up to10V, the maximum voltage of the output signal (Vout1) may
be adjusted in this menu point.
Note;
This also set the boost level (100 %).
E4:
Adjustment of Start Level.
The manual start level may be set at 3 different start values.
1)
Minimum level.
2)
Maximum level.
3)
Latest level of controller when turned off.
Note this functionality is only available when MultiController model choice (
E1
) is set to percentage.
Boost function (menu point
C3
) overrules start level adjustment.
E5:
Inverted output.
Option for inverting the output signal. E.g. 100% = 0V out / 1%=9,9V out.
E6:
Relay Shifting Point.
Setting of output voltage (Vout1) at which relay shifts from inactive to active.
If E6=0, then relay shifts when
regulator is activated.
If alarm function is activated (C8) and (E42= ALARM1) this menu point is obsolete.
E25-E28
These menu points set up control of MultiController setpoints via an external control signal. In E25/E26
the voltage range is defined. In E27/E28 the corresponding min. and max. voltage signals (in %) are defined.
E25:
Minimum voltage supplied by source of external control signal (voltage source) on Vin2.
E26:
Maximum voltage supplied by source of external control signal (voltage source) on Vin2.
E27:
Signal value at minimum.
Enter the corresponding minimum value in % (e.g. 0V=0%) of the voltage source at minimum (
E25
).
E28:
Signal value at maximum.
Enter the corresponding maximum value in % (e.g. 10.0V=100%) of the voltage source at maximum (
E26
).