LOYTEC electronics GmbH
file. This means also that all existing bindings may be lost and have to be recreated. To add
NVs to an existing configuration it is recommended using external NVs. Please refer to
Section 7.4.6 on how to extend an existing configuration without LNS.
Add L-Proxy Port x from XIF in non-LNS tool and create
bindings
L-Proxy Ports left to
configure?
yes
Start L-Proxy Configurator stand-alone
Section 7.9.2
Extract and save the port interface definition
Section 7.9.12
Make L-Proxy internal connections
Section 7.11
no
START
DONE
Download configuration to L-Proxy
Section 7.9.11
Upload/import port definitions
Section 7.9.12
Configure static NVs for Port x
Section 7.9.9
Export the port interface as XIF
Section 7.9.13
Enable Legacy NM Mode
Section 7.9.14
Tool supports
ECS ?
yes
no
Figure 65: Basic design-flow without LNS using static NVs.
7.4.5 Change an Existing Configuration with LNS
The recommended way to change an existing (probably static) port interface is to
add/delete dynamic network variables. Dynamic network variables in the Proxy functional
block or the virtual interface can be added and deleted without losing an existing binding in
NL-220, LonMaker, or Alex. The L-Proxy Configurator software synchronizes with the
added or deleted network variables. The work flow to change an existing configuration for
a specific port is shown in Figure 66.
Summary of Contents for L-Proxy
Page 1: ...L Proxy CEA 709 Gateway User Manual LOYTEC electronics GmbH ...