I418 GB F 04 15
G
B
8
P.11 ... P.18
– Function of output relays 1 ... 8:
OFF
= Not used.
1 .. 32
= Weight of the step. This relay drives a bank of cpacitors which power is n times (n = 1…32) the smallest power defined with parameter P.06.
ON
= Always on.
NOA
= Alarm normally de-energised. The relay is energised when any alarm with the Global alarm property arises.
NCA
= Alarm normally energised. The relay is de-energised when any alarm with the Global alarm property arises.
FAN
= The relay controls the cooling fan.
MAN
= Relay is energised when device is in MAN mode.
AUT
= Relay is energised when device is in AUT mode.
A01 ... A13
= The relay is energised when the specified alarm is active.
P.19
– Setpoint (target value) of the cosphi. Used for standard applications.
P.20
– Language of scrolling alarm messages.
ADVANCED MENU
CODE
DESCRIPTION
ACC
UoM
DEF
RANGE
P.21
Password enable
Adv
OFF
OFF
ON
P.22
User password
Usr
001
0-999
P.23
Advanced password
Adv
002
0-999
P.24
Wiring type
Usr
3PH
3PH three-phase
1PH single-phase
P.25
Step trimming
Usr
OFF
ON Enabled
OFF Disabled
P.26
Setpoint cle
Usr
0.00
0 – 0.10
P.27
Setpoint clearance -
Usr
0.00
0 – 0.10
P.28
Step insertion mode
Usr
STD
STD Standard
Lin Linear
P.29
Cogeneration cos
ϕ
setpoint
Usr
OFF
OFF /
0.50 IND – 0.50 CAP
P.30
Disconnection sensitivity
Usr
sec
OFF
OFF / 1 – 600
P.31
Step disconnection passing in MAN
Usr
OFF
OFF Disabled
ON Enabled
P.32
Capacitor current overload alarm threshold
Adv
%
125
OFF / 100…150
P.33
Capacitor overload immediate disconnection threshold
Adv
%
150
OFF / 100.. 200
P.34
VT primary
Usr
V
OFF
OFF / 50-50000
P.35
VT secondary
Usr
V
100
50-500
P.36
Temperature unit of measure
Usr
°C
°C °Celsius
°F °Fahrenheit
P.37
Fan start temperature
Adv
°
55
0…212
P.38
Fan stop temperature
Adv
°
50
0…212
P.39
Temperature alarm threshold
Adv
°
60
0…212
P.40
Step failure alarm threshold
Adv
%
OFF
OFF / 25…100
P.41
Maximum voltage alarm threshold
Adv
%
120
OFF / 90…150
P.42
Minimum voltage alarm threshold
Adv
%
OFF
OFF / 60..110
P.43
THD V alarm threshold
Adv
%
OFF
OFF / 1..250
P.44
THD I alarm threshold
Adv
%
OFF
OFF / 1..250
P.45
Hours maintenance interval
Adv
h
9000
OFF/1…30000
P.46
Bar-graph function
Usr
Kvar Kvar
ins/tot
ins/tot
Corr att/nom
Delta kvar att/tot
P.47
Default auxiliary measure
Usr
Delta
Deltakvar
kvar
V
A
Week TPF
Cap. Current
Temp
THDV
THDI
ROT
P.48
Backlight flashing on alarm
Usr
OFF
OFF
ON
P.49
Serial node address
Usr
01
01-255
P.50
Serial speed
Usr
bps
9.6k
1.2k
2.4k
4.8k
9.6k
19.2k
38.4k
P.51
Data format
Usr
8 bit – n
8 bit, no parity
8 bit, odd
8 bit, even
7 bit, odd
7 bit, even
P.52
Stop bits
Usr
1
1-2
P.53
Protocol
Usr
Modbus Modbus
RTU
RTU
Modbus ASCII
Modbus TCP