– Function of output relays 1 ... 8:

OFF

= Not used.

1 .. 32

= Weight of the step. This relay drives  a bank of cpacitors which power is n times (n = 1…32) the smallest power defined with parameter P.06. 

ON

= Always on.

NOA

= Alarm normally de-energised. The relay is energised when any alarm with the Global alarm property  arises. 

NCA

= Alarm normally energised. The relay is de-energised when any alarm with the Global alarm property arises.

FAN

= The relay controls the cooling fan. 

MAN

= Relay is energised when device is in MAN mode.

AUT

= Relay is energised when device is in AUT mode.

A01 ... A13

= The relay is energised when the specified alarm is active.

P.19

– Setpoint (target value) of the cosphi. Used for standard applications.

P.20

– Language of scrolling alarm messages.

ADVANCED MENU

CODE

DESCRIPTION

ACC

UoM

DEF

RANGE

P.21

Password enable

Adv

OFF

OFF

ON

P.22

User password

Usr

001

0-999

P.23

Advanced password

Adv

002

0-999

P.24

Wiring type

Usr

3PH

3PH three-phase

1PH single-phase

P.25

Step trimming

Usr

OFF

ON  Enabled

OFF  Disabled

P.26

Setpoint cle

Usr

0.00

0 – 0.10

P.27

Setpoint clearance -

Usr

0.00

0 – 0.10

P.28

Step insertion mode

Usr

STD

STD Standard

Lin Linear

P.29

Cogeneration cos

ϕ

setpoint

Usr

OFF

OFF /

0.50 IND – 0.50 CAP

P.30

Disconnection sensitivity

Usr

sec

OFF

OFF / 1 – 600

P.31

Step disconnection passing in MAN

Usr

OFF

OFF Disabled 

ON  Enabled

P.32

Capacitor current overload alarm threshold

Adv

%

125

OFF / 100…150

P.33

Capacitor overload immediate disconnection threshold

Adv

%

150

OFF / 100.. 200

P.34

VT primary

Usr

V

OFF

OFF / 50-50000

P.35

VT secondary

Usr

V

100

50-500

P.36

Temperature unit of measure

Usr

°C

°C °Celsius

°F °Fahrenheit

P.37

Fan start temperature

Adv

°

55

0…212

P.38

Fan stop temperature

Adv

°

50

0…212

P.39

Temperature alarm threshold

Adv

°

60

0…212

P.40

Step failure alarm threshold

Adv

%

OFF

OFF / 25…100

P.41

Maximum voltage alarm threshold

Adv

%

120

OFF / 90…150

P.42

Minimum voltage alarm threshold

Adv

%

OFF

OFF / 60..110

P.43

THD V alarm threshold

Adv

%

OFF

OFF / 1..250

P.44

THD I alarm threshold

Adv

%

OFF

OFF / 1..250

P.45

Hours maintenance interval

Adv

h

9000

OFF/1…30000

P.46

Bar-graph function

Usr

Kvar Kvar 

ins/tot

ins/tot

Corr  att/nom

Delta kvar  att/tot

P.47

Default auxiliary measure

Usr

Delta

Deltakvar

kvar

V
A

Week TPF

Cap. Current

Temp

THDV

THDI

ROT

P.48

Backlight flashing on alarm

Usr

OFF

OFF

ON

P.49

Serial node address

Usr

01

01-255

P.50

Serial speed

Usr

bps

9.6k

1.2k
2.4k
4.8k
9.6k

19.2k
38.4k

P.51

Data format

Usr

8 bit – n

8 bit, no parity

8 bit, odd

8 bit, even

7 bit, odd

7 bit, even

P.52

Stop bits

Usr

1

1-2

P.53

Protocol

Usr

Modbus Modbus 

RTU

RTU

Modbus ASCII

Modbus TCP

Summary of Contents for DCRL8

Page 1: ...nal und unter Befolgung der einschl gigen Vorschriften installiert werden Vor jedem Eingriff am Instrument die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zweck...

Page 2: ...n medium voltage applications Wide range power supply 100 440VAC Front optical programming interface galvanically isolated high speed waterproof USB and WiFi dongle compatible Programming from front p...

Page 3: ...the other measurements as usual While the display shows MAN it is possible to select the step to be switched on or off To select a step use the or buttons The selected step will flash quickly Press MO...

Page 4: ...P Number of equivalent steps Voltage V RMS voltage of the plant current V HI Maximum peak of measure Current A RMS current of the plant voltage A HI Maximum peak of measure Weekly PF WPF Weekly averag...

Page 5: ...module that have been mounted The expansion modules provide additional resources that can be used through the dedicated setup menus The setup menus related to the expansions are always accessible even...

Page 6: ...ernet menu CMD Access to Commands menu CUS Access to Custom menu SAVE Exits saving modifications EXIT Exits without saving cancel Press AUT to access the submenu When you are in a submenu the main dis...

Page 7: ...ring of current inputs must match the value set by this parameter All possible combinations of parameter P 05 are supported P 04 Reading the connection polarity of the CT AUT Polarity is automatically...

Page 8: ...point Usr OFF OFF 0 50 IND 0 50 CAP P 30 Disconnection sensitivity Usr sec OFF OFF 1 600 P 31 Step disconnection passing in MAN Usr OFF OFF Disabled ON Enabled P 32 Capacitor current overload alarm th...

Page 9: ...eyond which the integral delay for tripping of the overload alarm is zeroed causing the immediate activation of A08 alarm P 34 P 35 Data of VTs eventually used in the wiring diagrams P 36 Unit of meas...

Page 10: ...e properties settings of the active alarms ALARM DESCRIPTION CODE DESCRIPTION ALARM EXPLANATION A01 Undercompensation In automatic mode all the available steps are connected but the cosphi is still mo...

Page 11: ...red command with MAN or AUT Press and hold for three seconds if you want to execute the selected command DCRL8 shows OK with a countdown If you press and hold until the end of the countdown the comman...

Page 12: ...screw with a maximum torque of 0 5Nm In case it is necessary to dismount the device repeat the steps in opposite order For the electrical connections see the wiring diagrams in the dedicated chapter a...

Page 13: ...16 17 18 FU12 10A FU13 5A FU1 KM1 KM2 R FU2 FU8 TC1 K1 K2 K8 KM8 R R R R MT wiring Configuration with MT measurement and correction Voltage measure 3 ph to ph voltage reading L1 L2 L2 L3 L3 L1 on MT s...

Page 14: ...6 OUT 7 COM MAX 10A OUT 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 S1 S2 NC VOLTAGE INPUT 100 600V 50 60Hz AUX SUPPLY 100 400V 50 60Hz 2 5W 7VA B300 250V 5A AC1 1 5A 400V AC15 NO CONTACT TERMINAL...

Page 15: ...600V Rated impulse withstand voltage Uimp 9 5kV Power frequency withstand voltage 5 2kV Ambient conditions Operating temperature 20 60 C Storage temperature 30 80 C Relative humidity 80 IEC EN 60068...

Page 16: ...hpersonal und unter Befolgung der einschl gigen Vorschriften installiert werden Vor jedem Eingriff am Instrument die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei...

Page 17: ...programmation optique frontale isol e galvaniquement haute vitesse imperm able compatible avec dongle USB et WiFi Programmation sur le panneau frontal partir d un ordinateur ou d une tablette Smartpho...

Page 18: ...mme d habitude Quand l cran alphanum rique se trouve sur MAN il est possible d activer d sactiver manuellement les tapes Pour s lectionner les tapes utiliser les touches ou L tape s lectionn e clignot...

Page 19: ...t de r glage Tension V Tension RMS de ligne de l installation V HI Valeur de cr te maximale de la mesure Courant A Courant RMS de ligne de l installation A HI Courant maximum enregistr FP moyen WFP Fa...

Page 20: ...es d extension fournissent des ressources suppl mentaires qui peuvent tre exploit es gr ce aux menus de r glage d di s Les menus de r glage concernant les extensions sont disponibles m me si les modul...

Page 21: ...Sortie avec sauvegarde des modifications EXIT Sortie sans sauvegarde annuler Appuyer sur AUT pour acc der au sous menu s lectionn Quand on se trouve dans un sous menu l cran principal affiche le code...

Page 22: ...pondre ce qui est programm dans ce param tre Toutes les combinaisons avec le param tre P 05 sont support es P 04 Lecture de la polarit de branchement des TA AUT La polarit est automatiquement reconnue...

Page 23: ...Lin Lin aire P 29 Point de r glage cos cog n ration Usr OFF OFF 0 50 IND 0 50 CAP P 30 Sensibilit la d connexion Usr sec OFF OFF 1 600 P 31 D connexion chelons en passant en MAN Usr OFF OFF D sactiv O...

Page 24: ...el duquel le retard int gral d intervention de la surcharge est r initialis provoquant l intervention imm diate de l alarme P 34 P 35 Donn es des TV ventuellement utilis es dans les sch mas de branche...

Page 25: ...DES ALARMES CODE ALARME DESCRIPTION A01 Sous compensation En mode automatique toutes les tapes disponibles sont activ es mais cos phi reste plus inductif que le point de r glage A02 Surcompensation E...

Page 26: ...a touche pendant trois secondes pour ex cuter la commande La DCRL8 affiche OK et un compte rebours Si l on maintient la touche enfonc e jusqu la fin du compte rebours la commande est ex cut e En revan...

Page 27: ...ration pour les quatre clips Serrer la vis de fixation au couple maximum de 0 5 Nm Au besoin d monter l appareil desserrer les quatre vis et proc der dans l ordre inverse Pour les branchements lectriq...

Page 28: ...A FU13 5A FU1 KM1 KM2 R FU2 FU8 TC1 K1 K2 K8 KM8 R R R R Insertion sur MT Insertion avec mesures et rephasage sur MT Mesure de tension 3 mesures de tension encha n e L1 L2 L2 L3 L3 L1 sur tension moye...

Page 29: ...7 COM MAX 10A OUT 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 S1 S2 NC VOLTAGE INPUT 100 600V 50 60Hz AUX SUPPLY 100 400V 50 60Hz 2 5W 7VA B300 250V 5A AC1 1 5A 400V AC15 NO CONTACT DISPOSITION DES...

Page 30: ...1x107 1x105 op rations Isolation Tension nominale d isolation Ui 600V Tension nominale de tenue aux impulsions Uimp 9 5 kV Tension de tenue la fr quence d exercice 5 2 kV Conditions ambiantes Temp rat...

Reviews: