35
Serial Output - page 2
Baud
:- Select from 300,600,1200,2400,4800,9600,19200,38400, 57600,115200
dF
= Data Format = 8n1, 7n1, 7E1, 701
Prot
= Protocol = P1 (polled ASCII), P2 (Polled Modbus ASCII), C1 (Continuous), H1 (GPS)
Addr
= Address = 00 to FF
t.rEP
= Reply Delay time in milliseconds 00 to 99
t.Chr
= Character space timing in milliseconds 00 to 99
Protocol C1 – Continuous output
Meter sends: 8 characters<CR>
e.g.
20 20 20 20 20 2D 31 37 0D
(-17)
decimal position = 0
20 20 20 20 2D 31 2E 36 0D
(-1.6) negative value
20 20 20 20 20 31 2E 38 0D
(+1.8) positive value
20 20 20 20 20 20 4F 52 0D
(OR)
over range
20 20 20 20 20 20 55 52 0D
(UR)
under range
Protocol H1 - GPS clock data format for use with our ASR-GPS
Protocol P1 – Polled ASCII
Controller sends: <STX> ADDRH:ADDRL r <ETX> e.g. 02 46 37 72 03 ( to device F7)
Meter replies <STX> 8 characters <ETX>
e.g.
02 20 20 20 20 20 2D 31 37 03
(-17)
decimal position = 0
02 20 20 20 20 2D 31 2E 36 03
(-1.6) negative value
02 20 20 20 20 20 31 2E 38 03
(+1.8) positive value
02 20 20 20 20 20 20 4F 52 03
(OR)
over range
02 20 20 20 20 20 20 55 52 03
(UR)
under range
Protocol P2 – Polled ASCII Modbus
When you have finished setting the meter, put the lockout switch in its ON position now, to prevent
your settings from being changed.
DIGIT
OK
ALARMS
AL1
AL2
AL3
AL4
OUTPUT
0% 100%
B r i e f l y p r e s s t o g e t h e r
Lockout notes:
Cal Lock switch = OFF when changing. Switch Cal Lock to ON after changing