22
Linearisation - Direct scaling
Lin.O
Lin.O
Lin.1
Press OK to select
Press both left buttons briefly
You can now choose to have the
lineariser on or off
Choose a DIRECT Calibration method - See the Calibration methods page.
dir
dc v
Confirms you are in
Theoretical Cal mode
Confirms DC voltage
range.
If DC current, this display
will show DC A. If loadcell
this will be omitted
Se.00
rd.00
ad.pt
quit
Apply input for
known value 00.
Press OK when
done
Set Value for
display at point 0.
Press OK when
done
Press OK to select
Press OK if you want
to add another point
Press OK if you want
to quit / abort.
Press OK if you want
to finish and save.
SE.10
rd.10
quit
save
Apply input for
known value 10.
Press OK when
done
Set Value for
display at point 10.
Press OK when
done
Press OK to select
Press OK if you want
to quit / abort.
Press OK if you want
to finish and save.
You can set as many or few points
as you wish. 11 points available.
You can quit and Save with less than
11 points if you wish.
200 kg
200 kg
Apply several
known loads
and tell the
meter what it
should read
save
Lockout notes:
Cal Lock switch = OFF when changing. Switch Cal Lock to ON after changing