EXPANSION
VESSEL
SIZING
The WH19/WH21 unvented kit supplied with the EcoShield™ water heater includes an expansion vessel, this should be checked by the installer
to ensure there is sufficient spare capacity available for the Hot water secondary system volume. If not an additional correctly sized expansion
vessel should be installed, additional expansion vessels are available from Lochinvar Ltd.
EcoShield™
Unvented kit
required
Expansion vessel
supplied
Spare system expansion available
SHW35-245
WH19
V25
415litre
SHW46-325 SHW61-325
WH19
V25
338litre
SHW86-410 TO SHW146-410
WH21
V34
502litre
STANDARD
UNVENTED
SYSTEM
KIT
EXPANSION
VESSELS
The following information is based on an inlet pressure of 3.5 bar and an expansion vessel efficiency of 0.45 using a standard 6 bar unvented
kit. If the system will have different parameters a more detailed calculation will need to be made.
V V = S V * e
0.45
Where:
V V
=
Vessel Volume
S V
=
System Volume
e
=
Coefficient of Expansion
(See Table 10.1)
Stored Temp.
C
30
35
40
45
50
55
60
e
0.005
0.006
0.008
0.010
0.012
0.015
0.017
Stored Temp.
C
65
70
75
80
82
85
90
e
0.020
0.023
0.026
0.030
0.031
0.033
0.037
COEFFICIENT
OF
EXPANSION
OF
WATER
AT
3.5
BAR
INLET
PRESSURE
13.0
ELECTRICAL SUPPLY
Wiring external to the equipment must be installed in accordance with I.E.E. Regulations and any local regulations that apply.
Model
Normal Supply Voltage
External Fuse Rating
Power Consumption
SHW35-245CE
230V AC
50 Hz
1 PH
10 Amps
361W
SHW46-325CE
431 W
SHW61-325CE
459 W
SHW86-410CE
646 W
SHW116-410CE
932 W
SHW146-410CE
961 W
ELECTRICAL
SUPPLY
REQUIREMENTS
Warning: this appliance must be earthed
A suitably competent person must check wiring. Normal supply required is 230 volts’ AC, single phase, 50 hz.
An isolator with a contact separation of at least 3mm in all poles should be sited close to the equipment and
must only serve that equipment. The double pole switch must be readily accessible under all conditions
Summary of Contents for EcoShield SHW116-410CE
Page 2: ...2 ...
Page 9: ...9 EXPLODED VIEW DRAWINGS ...
Page 27: ...27 Max distance between brackets ...
Page 28: ...28 ...
Page 29: ...29 ...
Page 34: ...34 ...
Page 47: ...47 13 9 LADDER DIAGRAM LADDER DIAGRAM ...
Page 71: ...71 NOTES ...
Page 72: ...72 N ...