Excel
®
XR Series
Electronic Metering Pump
PROFIBUS DP-V0 Manual
Manual No.: 55313
Revision :
04
Rev. Date: 03/2020
Note: For enhanced control features see manual 54630 and enhanced control features see manual 54772
Page 1: ...el XR Series Electronic Metering Pump PROFIBUS DP V0 Manual Manual No 55313 Revision 04 Rev Date 03 2020 Note For enhanced control features see manual 54630 and enhanced control features see manual 54...
Page 2: ...24 Operation Mode Configuration 9 4 1 3 Modules 26 42 Timed Event Configuration 10 4 1 4 Modules 43 57 Input Output Configuration 11 4 1 5 Modules 58 64 System Settings 12 4 1 6 Modules 65 68 Read Onl...
Page 3: ...the LMI Chemical Resistance Chart for compatibility of your specific LMI metering pump Contact your local LMI distributor for further information Tubing Connections Inlet and outlet tubing or pipe si...
Page 4: ...annot occur Ground Fault Circuit Interrupter WARNING To reduce the risk of electric shock install only on a circuit protected by a Ground Fault Circuit Interrupter GFCI Line Depressurization To reduce...
Page 5: ...y a global network of highly trained field engineers and aftersales support The PROFIBUS DP interface conforms to the PROFIBUS DP V0 standard for cyclic data transmission This manual assumes the reade...
Page 6: ...display screen indicates there are more settings available on another page Figure 1 Display Navigation 3 2 Settings To access the settings screen Figure 2 press Settings in the home screen Navigate to...
Page 7: ...an be configured via software in the range of 1 125 The Internal Line Termination can also be enabled disabled on this screen The final device on the communication bus must have line termination enabl...
Page 8: ...associated operation mode Bit 0 Manual Local only Bit 1 Analog External Bit 2 Pulse External Bit 3 Batch External Bit 4 Cycle Timer Internal Bit 5 Timed Event Internal Input Output UINT8 2 Manual Flo...
Page 9: ...put Output UINT8 13 Batch Mode Volume XXXXX XX mL The valid range is 0 to 1000000 Input Output UINT32 14 Batch Mode Time Seconds Range is 1 86400 Input Output UINT32 15 Batch Mode Units Enumeration 0...
Page 10: ...31 Timed Event2 Start Time 4 decimal digit format HHMM Range HH Hour 00 23 MM Minute 00 59 Input Output UINT16 32 Timed Event2 Duration Integer representing minutes with a valid range of 1 1439 Input...
Page 11: ...Input 3 Config Enumeration with a range 0 5 The enumeration is as follows 0 Digital Input Disabled 1 Digital Input RemoteOnOff 2 Digital Input FloatSwitch_Empty 3 Digital Input FloatSwitch_Low 4 Digi...
Page 12: ...4 Digital Output AlarmOut 5 Digital Output INTEXTMode 6 Digital Output UserAlarmOut 7 Digital Output PumpStopped 8 Digital Output TimedEvent Input Output UINT8 56 Digital Output 2 State Enumeration 0...
Page 13: ...1 6 Modules 65 68 Read Only Version Information Module Name Description Direction Data Type 65 Main Firmware Version Range is 0 65535 as an integer that must be converted to hex to be read as 0000 FFF...
Page 14: ...ut UINT32 78 Totalizer User Volume Integer representing Gal or L depending on current unit setting Output UINT64 79 Totalizer User Hours Integer representing number of hours Output UINT32 80 Totalizer...
Page 15: ...t 7 Current Units 0 English 1 Metric Bit 8 Pump Calibration Status 0 No 1 Yes Bit 9 Keypad Locked Status 0 No 1 Yes Bit 10 Home Screen Displayed 0 No 1 Yes Bit 11 Batch Mode Dosing Active 0 No 1 Yes B...
Page 16: ...12 B Code connector with the following pin out Figure 5 Connector C Pin Diagram The M12 circular connector conforms to IEC 60947 5 2 or IEC 61076 2 101 per the PROFIBUS Interconnection Technology Guid...
Page 17: ...CABLE WIRING...
Page 18: ...correct Wiring 3 Verify wiring is correct per Figure 5 Connector C Pin Diagram 4 Pump not powered 4 Verify the pump is powered on Pump does not start when commanded via PROFIBUS 1 Homescreen is not di...
Page 19: ...nd specialty vehicle products and services across 40 respected brands designed to excel in even the most complex and harsh conditions where downtime is especially costly Our employees connect to custo...