background image

 

MIUM0014_REV01_ HP_20151009-MIUM-ENG 

1

 

 

 

 

 

 

 

I

I

N

N

S

S

T

T

A

A

L

L

L

L

A

A

T

T

I

I

O

O

N

N

,

,

 

 

O

O

P

P

E

E

R

R

A

A

T

T

I

I

O

O

N

N

 

 

A

A

N

N

D

D

 

 

M

M

A

A

I

I

N

N

T

T

E

E

N

N

A

A

N

N

C

C

E

E

 

 

M

M

A

A

N

N

U

U

A

A

L

L

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR TO AIR HEAT RECOVERY UNIT WITH BUILT-IN 

INVERTER DRIVEN COMPRESSOR HEAT PUMP 

 
 
 
 
 
 
 

SERIES  

HPH-HPR-HPS

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Summary of Contents for HPH 14

Page 1: ...ENG 1 I IN NS ST TA AL LL LA AT TI IO ON N O OP PE ER RA AT TI IO ON N A AN ND D M MA AI IN NT TE EN NA AN NC CE E M MA AN NU UA AL L AIR TO AIR HEAT RECOVERY UNIT WITH BUILT IN INVERTER DRIVEN COMPRE...

Page 2: ...ant surveillance LMF products therefore offer S Thank you once again for your preference The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing erro...

Page 3: ...ENTION AUTHORIZED PERSONNEL ONLY 1 INTRODUCTION pag 4 2 DIMENSIONS AND WEIGHTS pag 5 3 TRANSPORTATION HANDLING AND STORAGE pag 8 4 INSTALLATION CONNECTION pag 10 5 WIRING DIAGRAMS pag 13 6 ELECTRONIC...

Page 4: ...be installed in accordance with the laws in force in the country in which the unit is installed Unauthorized tampering with the electrical and mechanical equipment will VOID THE WARRANTY Check the el...

Page 5: ...Supply E Exhaust R Return F Fresh air HPH 14 20 26 50 92 144 205 A mm 2185 2185 2515 2845 3175 3505 3835 B 1030 1195 1360 1690 2020 2350 2350 C 1190 1190 1190 1520 1850 2180 2510 L 620 785 950 1280 16...

Page 6: ...h air HPR 14 20 26 50 92 144 205 A mm 2185 2185 2185 2185 2350 2350 2515 B 1030 1195 1360 1690 2020 2350 2350 C 1190 1190 1190 1520 1850 2180 2510 L 620 785 950 1280 1610 1940 1940 H 475 475 475 640 8...

Page 7: ...aust R Return F Fresh air HPS 14 20 26 50 92 144 205 A mm 2185 2185 2515 2845 3175 3505 3835 B 1030 1195 1360 1690 2020 2350 2350 C 1190 1190 1190 1520 1850 2180 2510 L 620 785 950 1280 1610 1940 1940...

Page 8: ...gloves helmets when handling the unit to avoid risk of injuries For the lifting and transportation of the unit use adequate equipment according to the 89 391 CEE regulations and further modifications...

Page 9: ...nded to avoid obstructions to air flow near or above the unit protect the unit from high winds that can favor or not the airflow protect the unit from heat sources or pollutants chimneys extractors pr...

Page 10: ...ce of the unit Respect the recommendations given by the producers of such products Before placing in function the unit check the perfect connection of the various components and the internal parts of...

Page 11: ...structure capable supporting the weight of the machine on each support point install vibration damper device in order to reduce vibration transmission Position the unit in a point where the condensat...

Page 12: ...does not interfere with discharge of the unit Livello cond en sa Co ndensate level Water coil connection optional CCS section The water heating or cooling coil CCS is supplied with GAS male threaded h...

Page 13: ...e MC00005 valid for all sizes 7 SCHEDULED MAINTENANCE It is the responsibility of the User to carry out all types of maintenance operations Only personnel previously trained and qualified may carry ou...

Page 14: ...ty For an automatic pressure drop limit control installation of filter pressure switches is recommended Yearly maintenance Check that all the electrical equipment in particular the fixing of the elect...

Page 15: ...akage In case of leakage previously empty the circuit and recover the refrigerant Remove the lower panel with built in handles fixed by panel locks to enter compressor compartment Fans Each fan sectio...

Page 16: ...correct Refrigerant leakage Required performance not met by compressor capacity Unit on defrost mode Compressor cooling capacity reduced because of too high condensing pressure Adjust the right tempe...

Reviews: