LXC63X0/LXC51X0
Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC63X0/LXC51X0
Generator controller user manual.
Dongguan Tuancheng Automation Equipment Co.,LTD.
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
6 of 36
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
6 of 36
3.
3.
3.
3.O
3.1.
3.1.
3.1.
3.1. K
K
K
Key
ey
ey
ey F
F
F
Function
unction
unction
unction
Stop/ Reset key
This button places the module into its Stop/reset mode.
When engine is running, pressing this key will stop the engine.
When a shutdown alarm occur, pressing this key will reset alarm.
Start key
In manual or manual test mode, pressing this key will start engine.
Manual mode key/
Config “-” key
Pressing this key will set the module into manual mode.
In setting parameter status, pressing this key will decease setting
value.
Manual test mode/
Config “+”key
Pressing this key will set the module into manual test mode.
In setting parameter status, pressing this key will increase setting
value.
Auto key /
Config “enter” key
Pressing this key will set the module into automatic mode.
In setting parameter status, pressing this key will shift cursor or confirm
setting value.
View history record
key
Press this button to display abnormal shutdown generator set records,
press the key again to exit.
Scroll key
In the parameter display and record query screen, press this key to
make a scroll operation.
3.2.
3.2.
3.2.
3.2. Automatic
Automatic
Automatic
Automatic start
start
start
start/stop
/stop
/stop
/stop operation
operation
operation
operation
Press
, its indicator lights, and controller enters Auto mode.
3.2.1
3.2.1
3.2.1
3.2.1 Starting
Starting
Starting
Starting Sequence
Sequence
Sequence
Sequence::::
1. LXC6320/5120:When Mains is abnormal (over and under voltage, over and under frequency, loss of
phase, phase sequence wrong), it enters into mains "abnormal delay" and LCD display count down time.
When mains abnormal delay is over, it enter into "start delay".
2. LXC6310/5110:Generator enters into "start delay" as soon as "Remote Start on Load" is active.
3. Start Delay timer is shown on Status page of LCD.
4. When start delay is over, preheat relay outputs (if this be configured), "preheat start delay XX s" is
shown in LCD.
5. When preheat delay is over, fuel relay outputs 1s and then start relay output; if engine crank fails during
"cranking time", the fuel relay and start relay deactivated and enter into "crank rest time" to wait for next
crank.
6. If generator crank fails within setting times, controller will send “Fail to start” and the warning will be
shown on LCD at the same time.
7. In case of successful crank attempt, "safety on timer" starts. During this period, low oil pressure, high
water temperature, under speed, charge failure alarms are disabled. As soon as this delay is over, "start
idle delay" is initiated (if configured).
8. During "start idle delay", under speed, under frequency, under voltage alarms are inhibited. When this
delay is over, "warming up delay" starts (if configured).