E1400 V2 Installation Guide
7.15 X19
X19
System
1
2
3
4
5
6
7
8
case
Do not connect
Do not connect
RS232 Rx
GND
GND
RS232 Tx
Do not connect
Do not connect
Shield
RJ-45
Use
isolated USB-RS232 converter (Art.-No. 0150-2473
or 0150-3120
)
for configuration over RS232.
7.16 X20
X20
Analog In (+-10V Differential Analog Input)
1
2
3
4
5
6
7
8
case
Do not connect
Do not connect
Analog In -
GND
GND
Analog In +
Do not connect
Do not connect
Shield
RJ-45
7.17 S5
S5
Bus Termination / AnaIn2 Pull Down
S5
Switch 6: Override Configuration Ethernet to DHCP
Switch 5: Bootstrap: Must be off for normal operation
Switch 4: CAN termination on ME (120R between pin 7 and 8 on X10/X11) on/off
Switch 3: CAN termination on CMD (120R between pin 7 and 8 on X7/X8) on/off
Switch 2: Termination resistor for RS485 on CMD (120R between pin 1 and 2 on X7/X8) on/off
Switch 1: AnIn2 pull down (4k7 Pull down on X4.4). Set to ON, if X4.4 is used as digital output.
Factory setting: all switches “on” except S5.5 (Bootstrap) and S5.6 (Override to DHCP)
Page 16/27
www.LinMot.com