ioPower User guide
Serial Command Set
Rev. 1.41 Copyright© All rights reserved.
Feb 2005
12
ED
– Timer
Activate everyday at a specific time point
[Description]Set the timer to turn on/off a specific
port every day at specific time
point
[Usage]
ED [
bank_number
] [
port_number
] [ON | OF] [
Time_point
]
[Examples]
ED 1 4 ON 02:12:20 – Set timer to power on port 4 on bank 1 exactly
every day at 02:12:20.
ED 1 0 ON 00:10:00 – Set timer to power on all ports on bank 1 exactly
every day at 00:10:00.
ED 0 0 OF 01:00:00 – Set timer to power off all ports on all cascaded
banks every day at 01:00:00.
Notes:
1. A port number of 0 represents all ports; while a bank number of 0 represents all
cascaded banks.
2. The command:
ED
0 0x ………, x = 1~9, is not valid.
EW
– Timer
Activate every week at a specific time point
[Description]Set the timer to turn on/off a specific
port every week at specific time
point
[Usage]
EW [
bank_number
] [
port_number
] [ON | OF] [
day
] [
Time_point
]
[Examples]
EW 1 4 ON 1 01:22:50 – Set timer to power on port 4 on bank 1 exactly
every Monday at 01:22:50..
EW 1 0 ON 3 00:10:00 – Set timer to power on all ports on bank 1 exactly
every Wednesday at 00:10:00.
EW 0 0 OF 5 01:00:00 – Set timer to power off all ports on all cascaded
banks every Friday at 01:00:00
.
Notes:
1. A port number of 0 represents all ports; while a bank number of 0 represents all
cascaded banks.
2. The command:
EW
0 0x ………, x = 1~9, is not valid.
3. A day of 0 represents Sunday; while a day of 1 represents Monday, later calculate
for this reason.
TQ – Timer Quit
[Description]Cancel a specific/all timer setting(s)
[Usage] TQ [
bank_number
] [
port_number
] [ON | OF]
[Examples]
TQ 1 4 ON – Cancel timer power-on setting on port 4 of bank 1
TQ 1 4 ON – Cancel timer power-on setting on port 4 of bank 1
TQ 0 4 - Cancel timer power-on&off setting on port 4 of bank 1
TQ 1 0 OF - Cancel timer power-off setting on all port of bank 1
TQ 0 0 ON - Cancel timer power-on setting on all port of all banks
TQ 0 0 - Cancel timer power-on&off setting on all port of all banks
Notes:
1. A port number of 0 represents all ports; while a bank number of 00 represents all
cascaded banks.
2. The command: TQ 0 x ………, x = 1~9, is not valid.
3. If you have not specified either “ON” or “OF” as the command parameter, it is
assumed that this Timer Quit directive will be directed on both the Power-ON and Power-
OFF setting of that specific port.