The control RS200L possesses an integrated protection circuit against uncontrolled movements. It is
activated if during normal operation an emergency stop signal is given to the dock leveller or if voltage
supply is interrupted. After release of the emergency stop or power up, the dock leveller the valve stay
closed, until the push button leveller up button is activated.
8. Overload protection
The control RS200L possesses an integrated overload circuit for the hydraulic unit. Each phase is
examined for overload. As soon as this is the case, the contactor switches automatically off. Further the
circuit is secured against phase failure. Both errors are signalled by the red LED LE1.
.
9. Error messages and rectification / LED
Error messages
Cause
Rectification
System does not respond
No mains power
Check mains power to control box
Leveller is not raising when
the UP button is operated.
interlock door
– leveller is
activated
Check interlock contact
Leveller is not raising when
the UP button is operated,
although motor is running
Field rotation is wrong
Swap two phase wires of the
hydraulic unit
Red LED ON
Overload protection is
activated
Check hydraulic unit, cabling and
fuses
10 Technical Data
Mains supply
3~ 400VAC, 50 Hz, +/- 10%
3~ 230VAC, 50 Hz, +/- 10%
Fuse supply voltage F1-F3
3 x 3,15A T at 400VAC
3 x 5A T at 230 VAC
Mains fuses
10A K- characteristic
Control voltage
24 VDC max. 0,9 A
Fuse control voltage (F4)
Resettable fuse 1,6 A
Maximal loads
Hydraulic unit
Max 2,2 KW 6 A
Valve
24 VDC +/- 10%, 0,6 A / 100%
Mounting
Vertical on the wall , min. height 100 cm
Housing dimensions
215 mm x 275 m x 190 mm
Ambient temperature
-
10° C … +55°C
Storage temperature
-
20°C … +85°C
Isolation class
IP 65
Weight
5,5 Kg
GB
7. Protection against uncontrolled movements
Page 7 / 8
–
RS 200L / LC-3157 Rev.A