The control RS200L possesses an integrated protection circuit against uncontrolled movements. It is 
activated if during normal operation an emergency stop signal is given to the dock leveller or if voltage 
supply is interrupted. After release of the emergency stop or power up, the dock leveller the valve stay 
closed, until the push button leveller up button is activated.  

 

8. Overload protection  

 

The control RS200L possesses an integrated overload circuit for the hydraulic unit. Each phase is 
examined for overload. As soon as this is the case, the contactor switches automatically off. Further the 
circuit is secured against phase failure. Both errors are signalled by the red LED LE1.  


 

9. Error messages and rectification / LED 

 

Error messages  

Cause 

Rectification 

System does not respond 

No mains power 

Check mains power to control box 

Leveller is not raising when 
the UP button is operated. 

interlock door 

– leveller is 

activated 

Check interlock contact 

Leveller is not raising when 
the UP button is operated, 
although motor is running 

Field rotation is wrong 
 

Swap two phase wires of the 
hydraulic unit 

Red LED ON 

Overload protection is 
activated 

Check hydraulic unit, cabling and 
fuses 

 

10 Technical Data 

 

Mains supply  

3~ 400VAC, 50 Hz, +/- 10% 
3~ 230VAC, 50 Hz, +/- 10% 

Fuse supply voltage F1-F3 
 

3 x 3,15A T at 400VAC 
3 x 5A T at 230 VAC  

Mains fuses  

10A K- characteristic  

Control voltage 

24 VDC max. 0,9 A 

Fuse control voltage (F4) 

Resettable fuse 1,6 A 

Maximal loads  
Hydraulic unit 

Max 2,2 KW 6 A 

Valve  

24 VDC +/- 10%, 0,6 A / 100% 

Mounting  

Vertical on the wall , min. height 100 cm  

Housing dimensions 

215 mm x 275 m x 190 mm 

Ambient temperature  

-

10° C … +55°C 

Storage temperature  

-

20°C … +85°C 

Isolation class  

IP 65 

Weight  

5,5 Kg 

 

   

GB

  

 7.  Protection against uncontrolled movements

 

Page 7 / 8

RS 200L / LC-3157 Rev.A