This directions for use contains following products:  

Rectangular Duct Fans SRF, SRF EC, LRF, LRF EC, IRF, MFF  

D E S C R I P T I O N  

 

The fan is used for transportation of "clean" air, mea-
ning  not  intended  for  fire-dangerous  substances, 
explosives, grinding dust, soot, etc. 

 

The fan is equipped with an asynchronous external 
rotor induction motor with maintenance-free sealed 
ball-bearings. 

 

The capacitor has finite lifetime and should be ex-
changed  after  45.000  operation  hours  (about  5 
years of operation) to secure maximum function. 
Defective capacitor can cause damage. 

 

To achieve maximum life time for installations in 
damp  or  cold  environments,  the  fan  should  be 
operating continuously. 

 

The fan can be installed outside or in damp envi-
ronments. Make sure that the fan-house is equipped 
with drainage. 

 

The fan is intended to be used with the voltage and 
frequency that's stated on the label on the fan. 

 

The fan can be installed in any position. 

 

I N S T A L L A T I O N  

 

The  fan  must  be  installed  according  to  the  air 
direction label on the fan. 

 

The fan must be connected to duct or equipped 
with a safety grille. 

 

The fan should be installed in a safe way and make 
sure that no foreign objects are left behind. 

 

The fan should be installed in a way that makes 
service and maintenance easy. N.B.! Consider the 
weight and size of the fan. 

 

The fan should be installed in a way that vibrations 
not can be transfused to duct or building. To provi-
de this, use for example a flange. 

 

To  regulate  the  speed  a  transformer  or  a  speed 
controller can be connected. 

 

A wiring diagram is applied on the inside of the 
junction box or separately enclosed. 

 

The fan is installed and connected electrically in the 
right way grounded and with motor protection. 

 

The  motor  protection  must  always  be  used,  see 
wiring diagram. 

 

Electrical  installations  must  be  made  by  an 
authorized electrician. 

 

Electrical  installations  must  be  connected  to  a 
locally  situated  tension  free  switcher  or  by  a 
lockable head switcher. 

 

O P E R A T I O N  

Before starting, make sure that: 

 

the  current  does  not  exceed  more  than +5%  of 
what is stated on the label. 

 

the connecting voltage is in b6% to —
10% of the rated voltage. 

 

no noise appears when starting the fan. 

 

the rotation direction at 3-phase motors are 
according to the label. 

 

H O W   T O   H A N D L E  

 

The fan must be transported in its packing until in 

• Attention, look out for sharp edges and corners.  

stallation. This prevents transport damages, scrat- 
ches and the fan from getting dirty. 

 