LIGHTSAFE EBLED2 Quick Start Manual Download Page 1

 EBLED2 Instructions Rev04 

 

 EBLED2 

   3 Hour Maintained Emergency Drop Light 

We are delighted that you have purchased this Light fitting. Please read this instruction manual before installation and retain 
for the user/maintenance engineer for future reference.  

 
Our  products  are  designed  to  comply  with  the  recommendations  of  BS  EN  60598-1:2008  code  of  practice  for  emergency 
lighting of premises and be installed by a competent person in accordance with the relevant wiring regulations. 

 

IMPORTANT NOTE:

  

Installation  must  be  carried  out  by  a  skilled/competent  electrician  who  is  familiar  with  the  appropriate  standards  and 
technical requirements of the appliance and also taking in to consideration the latest building regulations. 

 
Not suitable for use with dimmer switches, Install in accordance with I.E.E. Wiring Regulations. 

 
This product 

must be

 earthed and 

NOT

 be subject to an electrical insulation test (500/1000v) 

Please note: - The LED s contained in this fitting are not designed to be replaced.   
The fitting is an un-switched maintained fitting i.e. the LED lamp will be permanently lit and cannot be used a non-maintained 
operation.  
This luminaire is suitable only for indoor use in dry locations. If operation is required in damp, dusty or corrosive locations 
care must be taken to select a suitable fitting for the location. 

 

 

 

INSTALLATION 

Before starting the installation ensure that the electricity supply is isolated and that it cannot be re-energised accidentally 
 
1) Find a suitable location to install the fitting. 
 
2) Undo screws at either end of ceiling box and remove cover. 
 
3) Un plug multi connector and use the case of ceiling box as template and mount in required location. 
 
4) Thread mains cable through rear of case with appropriate cable protection, i.e. glanding and connect into terminal block 
and completing terminating connections. 
 
5) Re connect multi plug connector and re fit ceiling box cover with screws supplied. 
 
6) Restore the supply and check that the green LED indicator illuminates to confirm the batteries are charging 
 
7) Allow a short period for part charging of the batteries and then isolate the mains supply to the fitting in order to check the 
correct operation of the fitting in emergency mode. It is recommended to initially charge batteries for 36 hours from new to 
ensure full emergency duration is achieved. 

 
 

COMMISSIONING 

This  luminaire  has  an  integral  test  facility  located  on  the  side  of  the  fitting  indicated  by  3  LED’s.  To  check  the  Emergency 
operation of the fitting, press and hold the button marked test. The LEDs mark “C” and “T” should extinguish and the fitting 
should remain lit. The luminaire is now in emergency mode and is operating from the internal batteries. To return to normal 
operation release the test button the LEDs mark “C” and “T” should relight and the luminaire should remain lit. The luminaire 
is now back in its normal operation mode. 
 
Please note: - When in emergency mode the luminaire will not appear as bright as when in normal operation 

 

 