background image

Description

The ADC-ACC1-17-PSE is a single door access control unit 

featuring dual voltage power, an ADC-ACC1-17 controller, 

and a preinstalled adapter plate for an ADC-ACX1 single 

door reader board, housed in a 12”x14”x4.5” metal enclo-

sure with battery space.

Equipment List 

1.  Power Supply 24VDC / 3A (model: FPV4)
2.  Secondary 12V supply (model: B100)
3.  ADC-ACC1-17 controller
4.  Mounted ADC-ACX1 expansion back plate
5.  ADC-ACX1 mounting hardware 
6.  AC power cord

QUICK GUIDE  

ADC-ACC1-17-PSE

Bracket for

ADC-ACX1 or

ADC-ACC1-17

Accessories included

   •  AC power cord

   •  Battery harness

   •  Bracket mounting hardware

October 2017

1/2

www.lifesafetypower.com

Terminal Output Ratings

**Max currents listed are for individual terminals - total current at 12V and 24V not to exceed max rating of supply

Board

Terminal

Voltage

Max Current**

Notes

FPV4

DC OUT

24V

1.5A

Output can be switched by FAI Input on FPV4

AUX OUT

24V

0.75A

Max Current includes current drawn by B100

B100

DC OUT

12V

1.5A

For additional 12V devices

J2 (DC OUT)

12V

1.5A

For additional 12V devices

J5 (DC OUT)

12V

1.5A

For additional 12V devices

J1 (DC IN)

24V

0.75A

For additional 24V devices

J4 (DC IN)

24V

0.75A

For additional 24V devices

ADC-ACC1-17

VO

12V

0.65A

Max Current includes reader current draw

1-C (NO or NC)

24V

1.5A

Switched Lock Output - Ground at FPV4 DC OUT (-) Terminal

System Operation

The FPV4 power supply converts AC primary power to 24VDC for charging the battery set and powering the B100, locking 

device(s), and 24V auxiliary devices.  The B100 is powered from the FPV4 Auxiliary terminals and steps the 24V down to 

12V to power the ADC-ACC1-17 controller, reader(s), and any 12V auxiliary devices.
The battery set is charged by the red/black harness on the bottom edge of the FPV4.  The battery set MUST be two 12V 

batteries in series for a 24V battery set.  Observe polarity or damage to the system will occur.
Positive lock power is prewired to the ADC-ACC1-17 lock relay terminal 1C.  The lock positive should be wired to the NC 

(Fail Safe) or NO (Fail Secure) terminal as appropriate.  The lock negative should be wired directly to the FPV4 DC OUT (-) 

terminal to minimize noise and surges in the system.

101317_rev1

Reviews: