lifebreath.com
10
7
H
ANGING
S
TRAPS
The hanging straps are designed to reduce the possibility of noise, resonance, and harmonics.
Figure Callouts:
(1)
Screws (not included)
(2)
Washers (not included)
(3)
Hanging Strap Grommets
(4)
Structure
(5)
Machine Screws
(6)
“S” Hooks
(7)
Hand Loops
Installation Steps:
1.
Insert 4 screws and 4 washers (not included)
through the hanging strap grommets. Fasten
to the structure.
2.
Remove the 4 machine screws located on the
upper side of the unit. Attach the “S” hooks
and reinsert the machine screws.
3.
Hook the bottom grommets of the straps
through the “S” hooks. Pull down vertically
on the hand loops while lifting the bottom of
the unit.
4.
Level the unit from right to left to right and
front to back. Adjust the unit up by pulling
down vertically on the hand loops while
lifting on the bottom of the cabinet.
5.
Fold the excess strap of the hand loops and
secure with a zip tie.
Attention
•
The washer must be wider than the eyelet of the grommet on the hanging strap.
•
Must push up on the bottom of the HRV when pulling the hanging straps.
•
The unit must be mounted level for proper drainage of the condensate pans.