It is recommended that a licensed electrician make all electrical connections. It is very important that
the unit be properly grounded. The circuit must be sized to handle the Full Load Amperage (FLA)
indicated on the name tag for the circuit.
.
Maximum AMP Rating
HIGH
MED.
LOW
1230ERV
9.4
6.0
4.5
730ERV
4.5
3.2
2.4
530ERV
3.2
-
2.4
330ERV
2.0
1.4
1.0
Warning
•
Verify the polarity of the power coming into the unit with a test lamp or multimeter. Connect the
multimeter or test lamp probe to the wire being tested and the other probe to ground. The black
line should be “live”. If the white line is “live” the polarity is reversed and must be corrected. If
both lines are live, the voltage is not 120VAC. The black open line from the unit should be
connected to the live line and the white open line should be connected to the neutral line. Some
unit have a safety disconnect rocker switch located just outside of the electrical control box area.
The switch disconnects the live line. Verify that it is working properly with a multimeter or test
lamp. Always ensure the ERV is properly grounded before and after testing.
Caution
•
The ERV is designed to operate with ducting. When first starting the ERV, measure the amp draw to
each motor at each speed to ensure it is operating at or below the max rating.
Summary of Contents for 1230 ERV
Page 1: ......
Page 6: ...www lifebreath com 5 3 DIMENSIONAL DRAWINGS 330ERV Dimensions 530ERV Dimensions ...
Page 7: ...www lifebreath com 6 3 DIMENSIONAL DRAWINGS 730ERV Dimensions 1230ERV Dimensions ...
Page 32: ...www lifebreath com 31 18 WIRING DIAGRAMS 330ERV ...
Page 33: ...www lifebreath com 32 17 WIRING DIAGRAMS 530ERV ...
Page 34: ...www lifebreath com 33 17 WIRING DIAGRAMS 730ERV AND 1230ERV ...