www.lifebreath.com
29
16
T
ROUBLESHOOTING
Refer to the following table for troubleshooting the ERV unit.
Table 17.1 – Troubleshooting Procedures
SYMPTOM
CAUSE
SOLUTION
Poor airflows
•
1/4 in. (6mm) mesh on outside
hood is plugged
•
Filters plugged
•
Core obstructed
•
House grilles closed or blocked
•
Dampers are closed if installed
•
Poor power supply at site
•
Ductwork is restricting ERV
•
Improper speed control setting
•
ERV airflow improperly
balanced
•
Clean exterior hoods or vents
•
Remove and clean filter
•
Remove and clean core
•
Check and open grilles
•
Open and adjust dampers
•
Have electrician check supply voltage
•
Check duct installation
•
Increase the speed of the ERV
•
Have contractor balance ERV
Supply air feels cold
•
Poor location of supply grilles,
the airflow may irritate the
occupant
•
Outdoor temperature extremely
cold
•
Locate the grilles high on the walls or
under the baseboards, install ceiling
mounted diffuse or grilles so as not to
directly spill the supply air on the
occupant (i.e. over a sofa)
•
Turn down the ERV supply speed. A
small duct heater (1 kW) could be used
to temper the supply air
•
Placement of furniture or closed doors
is restricting the movement of air in the
home
•
If supply air is ducted into furnace
return, the furnace fan may need to run
continuously to distribute ventilation air
comfortably
Summary of Contents for 1230 ERV
Page 1: ......
Page 6: ...www lifebreath com 5 3 DIMENSIONAL DRAWINGS 330ERV Dimensions 530ERV Dimensions ...
Page 7: ...www lifebreath com 6 3 DIMENSIONAL DRAWINGS 730ERV Dimensions 1230ERV Dimensions ...
Page 32: ...www lifebreath com 31 18 WIRING DIAGRAMS 330ERV ...
Page 33: ...www lifebreath com 32 17 WIRING DIAGRAMS 530ERV ...
Page 34: ...www lifebreath com 33 17 WIRING DIAGRAMS 730ERV AND 1230ERV ...