Many buildings have ceiling return air plenum as in Figure B. Fresh air from the HRV can be introduced directly
into the ceiling space, but this should occur near the air handler’s intake.
By operating the HRV on a 24 hour/7 day battery backed timer, the unit can be set to operate only when
occupancy or indoor conditions require the air exchange.
In installations where it is satisfactory to provide general exhaust from the space, the air to be exhausted may
be taken directly from the return air plenum to the HRV as it is drawn back to the air handler. Fresh air
supplied by the HRV is then introduced directly into the return air plenum but at a location closer to the air
handler. The air handler would have a constant running blower to effectively distribute the fresh air and
remove the stale air. Balancing dampers would be in both the HRV supply and exhaust ducts between the
return air plenum and the HRV.
Warning
•
At no time should the air handler Total External Static Pressure (TESP) on the return duct exceed that of the
HRV.
•
When interlocking a rooftop unit with an ERV take care to ensure the fans of both units operate in the
correct rotation.
Figure B
Note:
Example configuration only.
Summary of Contents for 1200DD
Page 1: ......
Page 6: ...www lifebreath com 3 3 DIMENSIONAL DRAWINGS 455FD DD Dimensions 650FD DD Dimensions ...
Page 7: ...www lifebreath com 4 3 DIMENSIONAL DRAWINGS 700FD DD Dimensions 1200FD DD Dimensions ...
Page 35: ...www lifebreath com 20 25 WIRING DIAGRAMS 455FD ...
Page 36: ...www lifebreath com 21 25 WIRING DIAGRAMS 650FD 700FD 1200FD ...
Page 37: ...www lifebreath com 22 25 WIRING DIAGRAMS 455DD 650DD 700DD 1200DD ...