Operating the UPS
50
3.3. Transferring to Battery Mode
The UPS operates in Normal mode unless the mains/utility power fails or it is performing a battery self test,
then it automatically transfers to Battery mode for the back-up time available or the mains/utility power is
restored. Once input power is restored, the UPS returns to Normal mode
.
• Battery back-up run times are listed in
3.4. Transferring from Normal to Bypass Mode
Press and hold the power button for 2 seconds.
If the bypass power is within normal operating range, the option to continue to turn ON to bypass displays:
a. Use the arrow buttons to select Turn ON to bypass, and press
Enter
.
b.
Use the arrow buttons to select Yes, then press
Ente
r to confirm.
If the bypass power is outside normal operating range, the option turn-off the UPS displays. Use the arrow
buttons to select No or Yes, then press
Enter
to confirm.
3.5. Transferring from Bypass to Normal Mode
Press and hold the power button for 2 seconds.
If the UPS is operating normally, without faults, the option to continue to turn on UPS or turn off output displays:
a. Use the arrow buttons to select Turn on UPS, and press
Enter
.
b.
Use the arrow buttons to select Yes, then press
Enter
to confirm.
• The UPS automatically switches back to normal mode after an “overheated” or “overloaded” fault is
cleared and normal power is restored.
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...