Vertiv | Liebert® GXT5™ | Installer/User Guide
113
MODEL GXT5-
8000IRT5UXLN
*
8000IRT5UXLE
10KIRT5UXLN
*
10KIRT5UXLE
RATING
8000 VA/8000 W
10000 VA/10000 W
Agency
Safety
*
IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
EMI/EMC/C-Tick
EMC
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A)
CISPR22 Class A (RFI)
ESD
IEC/EN EN61000-4-2, Level 4, Criteria B
Radiated
Susceptibility
IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast
Transient
IEC/EN EN61000-4-4, Level 4, Criteria B
Surge Immunity
IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62.41 Category B
Transportation
ISTA Procedure
1
E
Table 7-6 UPS Specifications, 16-kVA and 20-kVA models
MODEL GXT5-
16KIRT9UXLN
*
16KIRT9UXLE
20KIRT9UXLN
*
20KIRT9UXLE
RATING
16000 VA/16000 W
20000 VA/20000 W
Dimensions, D×W×H, in. (mm)
Unit
430 × 630 × 394 (16.9 × 24.8 × 15.5)
Shipping
800 × 1200 × 710 (31.5 × 47.2 × 27.9)
Weight, kg (lb)
Unit
135.2 (298)
Shipping
190 (418.9)
186.7 (411.6)
190 (418.9)
186.7 (411.6)
Input AC Parameters
Operating
Frequency,
Nom.
50 or 60 Hz (factory-default is 50 Hz)
Factory-default
VAC
230 VAC
Operating voltage
range without
battery
operation
176 to 288 VAC (100 to 176 VAC with power derating)
Maximum
Allowable
VAC
288 VAC
Input frequency
without battery
operation
40 to 70 Hz
Input Power
Connection
Input terminal block
*Only these models are available in the ASIA PACIFIC region.
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...