Vertiv | Liebert® GXT5™ | Installer/User Guide
103
Table 6-3 Troubleshooting
PROBLEM
CAUSE
SOLUTION
UPS fails to
start
UPS is short- circuited or
overloaded
Ensure UPS is Off. Disconnect all loads and ensure nothing is
lodged in output receptacles. Ensure loads are not defective or
shorted internally.
Batteries are not charged
enough or not connected
Check to ensure the internal battery is connected. If it is not, fully
remove and reinstall the battery, and try to start the unit. If the
battery is connected, leave the UPS connected to input power for
24 hours to recharge batteries, then try to start the unit.
UPS has
reduced battery
backup time
Batteries are not fully charged
Keep UPS plugged in continuously at least 24 hours to recharge
batteries.
UPS is overloaded
Check load level indicator and reduce the load on the UPS.
Batteries may not be able to
hold a full charge due to age
Replace batteries. Contact your Vertiv representative or Vertiv
Technical Support for replacement battery kit.
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...