Liebert UPStation GXT 2U User Manual Download Page 1

AC Power Systems

For Business-Critical Continuity™

Liebert

®

 GXT2U

User Manual - 120V, 500-3000VA

DISCONTINUED 

PRODUCT

Summary of Contents for UPStation GXT 2U

Page 1: ...AC Power Systems For Business Critical Continuity Liebert GXT2U User Manual 120V 500 3000VA DISCONTINUED PRODUCT ...

Page 2: ...DISCONTINUED PRODUCT ...

Page 3: ...LLATION 8 4 1 Preparation 8 4 2 Tower UPS Installation 8 4 3 Rack Mount UPS Conversion and Installation 9 4 4 External Battery Cabinet Installation 13 5 0 CONTROLS AND INDICATORS 14 5 1 ON Alarm Silence Manual Battery Test Button 14 5 2 Standby Manual Bypass Button 15 5 3 Load Battery Level Indicators 4 Green 1 Amber 15 5 4 Fault Indicator LED Red 15 5 5 Bypass Indicator LED Amber 15 5 6 UPS ON In...

Page 4: ... Pin 6 Logic 21 7 4 UPS Intelligent Communications 22 8 0 CONFIGURATION PROGRAM 23 8 1 Liebert GXT2U Configuration Program Abilities 23 8 1 1 What You Will Need 23 9 0 MAINTENANCE 24 9 1 Battery Replacement 24 9 1 1 Internal Battery Replacement Procedures 25 9 2 Fuse Replacement 26 10 0 TROUBLESHOOTING 27 11 0 SPECIFICATIONS 32 12 0 BATTERY CABINET SPECIFICATIONS 34 13 0 BATTERY RUN TIMES 35 14 0 ...

Page 5: ... GXT2U Series complies with the limits for a CLASS A DIGITAL DEVICE PURSUANT TO Part 15 of FCC rules Operation is subject to the fol lowing two conditions 1 This device may not cause harmful interfer ence and 2 this device must accept any interference received including interference that may cause undesired operation Operating this device in a residential area is likely to cause harmful interferen...

Page 6: ...sert any object into the ventilation holes or other openings of the UPS DO NOT CONNECT equipment that could overload the UPS or demand half wave rectification from the UPS for example electric drills vacuum cleaners laser printers or hairdryers Storing magnetic media on top of the UPS may result in data loss or corruption Turn the UPS off and isolate the UPS before cleaning use only a soft cloth n...

Page 7: ...es caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Standby i DISCONTINUED PRODUCT ...

Page 8: ... regulates its output voltage whether utility power is present or not It supplies connected equipment with clean sinewave power Sensitive electronic equipment operates best from sinewave power For ease of use the Liebert GXT2U features a light emitting diode LED display to indicate either load percentage or battery capacity depending upon the mode of operation It also provides self diagnostic test...

Page 9: ...newave input current achieves two objectives The utility power is used as efficiently as possible by the UPS The amount of distortion reflected on the utility is reduced This results in cleaner power being available to other devices in the building not being protected by the Liebert GXT2U 3 3 INVERTER In normal operation the inverter utilizes the DC output of the power factor correction circuit an...

Page 10: ...ries To maintain battery design life operate the UPS in an ambient temperature of 68 F to 77 F 20 C to 25 C Optional external battery cabinets are available to extend battery run times 3 7 DYNAMIC BYPASS The Liebert GXT2U provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction Should the UPS have an overload overtemperature or UPS failure condi...

Page 11: ... GXT2U REAR VIEW Rev USBCARD Input Fuse Circuit Breaker AC Input Support Base Output Receptacles External Battery Connector Cooling Fan USB card being fitted in Liebert IntelliSlot Port DB 9 Communications Port DISCONTINUED PRODUCT ...

Page 12: ...be installed in either a tower configuration or in a rack depending on available space and use considerations Determine the type of installation and follow the appropriate instructions in either 4 2 Tower UPS Installation or 4 3 Rack Mount UPS Conversion and Installation 4 2 TOWER UPS INSTALLATION When using the Liebert GXT2U in a tower configuration use the included support base shown below left ...

Page 13: ...ardware from the rack mounting kit P N RMKIT18 32 Bracket assemblies are interchangeable between left hand or right hand Remove inner member of each bracket assembly as shown at right by extending it to its outermost position depressing the retaining latch and then pulling inner member from bracket assembly NOTE When rack mounted the UPS must be supported by a shelf brackets or slide rails on each...

Page 14: ... rails 4 Locate eight 8 M4 screws and eight 8 M4 nuts from hardware pack in this kit Each nut has a locking nylon insert that begins gripping the screw when it is halfway tight Make sure to tighten nut and screw completely to assure locking action Fasten rear member and front member together using four 4 screws and four 4 nuts per bracket assembly as shown in the figures at right For maximum suppo...

Page 15: ...embers attached from Step 5 into bracket assemblies by inserting top and bottom edges of inner members into the top and bottom curved tracks of front members and sliding the equipment into rack see figure in Step 6 Ends of inner members are tapered to allow rear of the equipment to be angled upward before insertion if space allows Then the rear bottom edges of inner members can be placed into fron...

Page 16: ...y oriented front panel overlay for rack mounting Snap the front bezel back into place 10 Once the UPS is installed in the rack the load may be connected Ensure the load equipment is turned off plug all loads into the output receptacles on the rear of the UPS 11 Plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with national and local electr...

Page 17: ...or Liebert representative for these additional options and any assistance needed Fasten the slides into position with the screws per the instructions included with the slide rails 4 Use the enclosed support bases for the tower option to prevent tip over One additional set of support base extensions ships with each external battery cabinet 5 Connect the supplied external battery cabinet cable to th...

Page 18: ...rm system to alert of additional problems Manual Battery Test To initiate a manual battery test press the ON button for at least one second while operating from utility power with no alarm conditions present If only three of the five Battery LEDs illuminate allow the UPS to recharge the batteries for 24 hours After 24 hours retest the batteries After the batteries have been retested if only three ...

Page 19: ... initiate the battery test 5 4 FAULT INDICATOR LED RED The Fault indicator LED is illuminated if the UPS has detected a problem Also one or more of the load battery level indicators may be illuminated refer to 10 0 Troubleshooting 5 5 BYPASS INDICATOR LED AMBER The Bypass indicator LED is illuminated when the UPS is operating from bypass power An alarm will sound indicating the UPS detected a prob...

Page 20: ...output voltage to match the utility via the Liebert GXT2U Configuration Program provided with the UPS The settings to choose from are 100 110 115 120 and 127 VAC output The factory default setting is 120 VAC CAUTION Never change the voltage settings while the UPS is ON and powering connected loads NOTE Setting output voltage to 100 VAC will cause the UPS unit to be derated 500 700 1000 VA to 90 15...

Page 21: ...ove on the UPS output 6 2 BYPASS MODE OPERATION Bypass mode occurs when the OFF button is pressed once while the UPS is in Normal Mode During bypass operation utility power provides energy to the UPS The utility power bypasses the inverter and provides power for the connected load The four green load level LEDs indicate an approximate level of load in 25 increments If the UPS becomes loaded beyond...

Page 22: ...te battery run times refer to 13 0 Battery Run Times The times listed in these tables are approximate based on resistive load and an ambient temperature of 77 F 25 C To increase this time turn off non essential pieces of equipment such as idle com puters and monitors or add the optional external battery cabinet If the UPS is manually turned OFF it must be manually restarted after utility power is ...

Page 23: ...t on pins 1 7 8 and 9 is 60VDC 10 0 mA Pin Assignment Description 1 Low Battery open collector 2 UPS TxD typical RS 232 levels 3 UPS RxD typical RS 232 levels 4 Remote Shutdown 5 12VDC 10 24 mA max battery operation 5 Common 6 Remote Shutdown short to pin 5 all modes of operation 7 Low Battery open emitter 8 Utility Fail open emitter 9 Utility Fail open collector Pin Assignment Collector to Emitte...

Page 24: ...tdown signal for 1 5 seconds the command cannot be canceled 3 A battery shutdown signal on Pin 4 will NOT cause an immediate shutdown A shutdown signal will start a 2 minute shutdown timer The timer cannot be stopped After 2 minutes the UPS will shut down 4 If the utility returns during the 2 minute timer countdown the shutdown timer will continue until the end of 2 minutes and the UPS will turn O...

Page 25: ...t be changed If the configuration program is used with an earlier UPS model with an earlier UPS firmware version that does not support the modifica tion of these settings the Options tab will display a reminder of the factory default settings These cannot be changed WARNING Note that when this option is selected and the UPS output is disabled using Pin 6 the UPS output can turn on automatically an...

Page 26: ...b site www lie bert com or contact your local dealer or Liebert representative Several option cards are available for use in the Liebert IntelliSlot port of the Liebert GXT2U The Liebert IntelliSlot SNMP Web Card provides SNMP and Web based monitoring and control of the UPS across the network The Liebert IntelliSlot MultiPort 4 Card allows you to install Lie bert MultiLink software on four compute...

Page 27: ...products Modify the shutdown setting of DB 9 pin 6 for information on pin assignments see 7 0 Communications 8 1 1 What You Will Need Using this program requires a computer running Windows 95 through Server 2003 as well as the configuration program disk and serial cable included in the UPS accessory box Use the serial cable beige or tan 3 wire GND TX RX straight through 2 2 3 3 5 5 to connect the ...

Page 28: ... safety cautions before proceeding Contact your local dealer or Liebert representative to obtain the appropriate replacement battery kit part number and pricing 9 1 BATTERY REPLACEMENT CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed before replacing the batteries Remove rings watches or other metal objects Use a P...

Page 29: ...he front of the UPS 5 Unpack the new battery assembly taking care not to destroy the packing Compare new and old battery assemblies to make sure they are the same If so proceed with Step 6 otherwise STOP and contact your local dealer Liebert representative or the Liebert Worldwide Support Group 6 Line up and slide in the new replacement battery pack 7 Reconnect the two slotted battery connectors a...

Page 30: ...ll assembly into the UPS Twist by hand rotate clockwise until fuse holder locks into position 4 Reconnect the input power cord to input AC supply 5 Restart the UPS The UPS is ready for normal operation CAUTION Before changing the input fuse turn off the UPS and unplug the supply lead from the AC input supply Replace the fuse with the same type and rating DISCONTINUED PRODUCT ...

Page 31: ...ass due to DC bus overvoltage beep every 4 sec C LED On bypass due to control power supply failure beep every 4 sec D LED On bypass due to PFC failure beep every 4 sec E LED On bypass due to inverter failure beep every 4 sec A C LEDs UPS failed battery test long beep every minute C E LEDs UPS shutdown due to command from communication port SNMP no beep Battery LED Flashing Internal Battery source ...

Page 32: ...attery indicator LED is illuminated UPS not plugged in UPS is operating from battery mode make certain UPS is securely plugged into the wall receptacle UPS input protection fuse has blown opened UPS is operating from battery mode Save data and close applications Replace UPS input fuse then restart UPS Utility voltage out of UPS input range UPS is operating from battery mode Save data and close app...

Page 33: ...ltage UPS requires service Contact your local dealer Liebert representative or the Liebert Worldwide Support Group Fault and Bypass indicator LEDs and diagnostic LED C are illuminated UPS control power supply fault UPS requires service Contact your local dealer Liebert representative or the Liebert Worldwide Support Group Fault and Bypass indicator LEDs and diagnostic LED D are illuminated UPS PFC...

Page 34: ...start flashing even if the input wiring is changed Contact a qualified electrician to verify site wiring Battery LED is flashing Battery source is not available continuous horn Check battery connections completely power down and restart UPS NOTE If the battery circuit opens while the UPS is running it will be detected when the next battery test is performed Bypass LED is flashing Bypass voltage is...

Page 35: ...n time remaining Output Overload bypass One short beep every half second Overtemperature bypass A one second beep every 4 seconds DC Bus Overvoltage bypass A one second beep every 4 seconds Control Power Supply Failure bypass A one second beep every 4 seconds PFC Failure bypass A one second beep every 4 seconds Inverter Failure A one second beep every 4 seconds Battery Test Failure A 2 second beep...

Page 36: ...plug 6 ft attached w NEMA 5 15 plug 10 ft attached w NEMA 5 15 plug OUTPUT AC PARAMETERS Output Receptacles 6 NEMA 5 15R Voltage 100 110 115 120 127 user configurable VAC 3 Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Qty x V x Rating 4 x 12V x 7 0 or 7 2 AH B...

Page 37: ... NEMA 5 15R 6 5 20R T Slot accepts 15A plug 6 5 20R T Slot 1 NEMA L5 30R on 12 in cord Voltage 100 110 115 120 127 user configurable VAC 3 Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Qty x V x Rating 4 x 12V x 7 0 or 7 2 AH 4 x 12V x 9 0 AH 6 x 12V x 9 0 AH B...

Page 38: ...2 3 102 5 46 5 BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Qty x V x Rating 2 x 4 x 12V x 7 0 or 7 2 AH 2 x 6 x 12V x 9 0 AH Battery Mfg Part China Storage Battery CSB 1270 F2 Panasonic UP VW1245P1 Yuasa REW 45 12 Backup Time See 13 0 Battery Run Times ENVIRONMENTAL Operating Temp 32 F to 104 F 0 C to 40 C Storage Temp 5 F to 122 F 15 C to 50 C Relative Humidity 0 to 95 non cond...

Page 39: ...82 240 40 665 464 272 224 133 168 50 534 352 200 160 98 128 60 421 280 152 120 84 88 70 356 232 128 96 70 72 80 300 192 104 80 56 64 90 265 160 96 64 49 56 100 231 136 88 56 42 40 Internal Battery 3 External Battery Cabinets minutes 10 5929 2976 2292 1728 560 1092 20 2179 1380 1044 636 330 552 30 1293 948 576 456 260 360 40 998 696 408 336 190 252 50 801 528 300 240 140 192 60 632 420 228 180 120 ...

Page 40: ...r warranty protection Visit the Quick Links section of our Web site at http www liebert com Click on Product Warranty Registration and fill in the form If you have any questions please contact us at US 800 222 5877 Outside the US 614 841 6755 upstech liebert com DISCONTINUED PRODUCT ...

Page 41: ...NOTES DISCONTINUED PRODUCT ...

Page 42: ...DISCONTINUED PRODUCT ...

Page 43: ...DISCONTINUED PRODUCT ...

Page 44: ...Asia 7 F Dah Sing Financial Centre 108 Gloucester Road Wanchai Hong Kong 852 2572220 Fax 852 28029250 The global leader in enabling Business Critical Continuity Business Critical Continuity Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co 2007 Emerson Electric Co AC Power Systems Connectivity DC Power Systems Integrated Cabinet Soluti...