10. Any distributor longer than 3 feet (1 meter)

should be supported at its end with a threaded
rod through top or bottom of duct. See Figure
#10.

11. It is recommended that single distributors are

mounted near the bottom of the duct to ensure
the steam is dispersed into the majority of the
air flow. See Figure #12.

12. Using duct mounting template provided, cut a

hole in side of duct just large enough to admit
steam manifold and condensate drain pipe
assembly. Use four sheet metal screws to
attach mounting plate to side of duct. See
Figure #11 and #12.

13. With multiple steam distributors, the top steam

distributor should be at least 8" below top of
duct to avoid possible condensation on
surface of duct. The remainder of space

below is proportioned accordingly. See Figure
#14. For short steam absorption systems see
Figure #13.

PLUMBING

All water supply and drain line connections

should be installed in accordance with local
plumbing codes.

WATER SUPPLY LINE

1.

Humidifier is intended to operate on potable
(cold) tap water.

2.

If the raw water is very hard, Liebert can
provide longer cylinder life on softened water.
However, softened water is more conductive
and more corrosive. Some hardware and/or
software changes may be required, at time of
order or in the field. Consult local
representative.

3.

DO NOT use a hot water supply to humidifier.
Minerals will adhere more easily to surfaces
and the fill valve’s small flow regulating orifice
could become plugged.

4.

Standard fill valves are sized for water
pressure ranging from 30 to 150 psig. For
other pressures, consult local representative.
This pressure should be measured at the
humidifier if the water pressure is suspect.

- 5 -

H

4"

4"

8"

MIN. H = 16"

1/3

1/3

1/3

2/5

2/5

1/5

Min. W = 12"

4"

4"

4"

H 20"
W 17"

Figure #14

Multiple Steam Distributors for Better Mixing

Figure #12

Single Steam Distributor Installation

8"

Steam Header

Figure #13

Multiple Steam Distributors

Summary of Contents for SGH Steam

Page 1: ...Steam Generating Humidifier Installation and Operation Guide IMPORTANT Read and save this guide for future reference This guide to be left with equipment owner SL 14050 Form 99 428 Rev 1 150 1633 Rev...

Page 2: ...E SUPPLY WIRING TO HUMIDIFIER 9 PRIMARY VOLTAGE SUPPLY WIRING FROM HUMIDIFIER S TO BLOWER PACKS 9 LOW VOLTAGE CONTROL WIRING 9 On Off Controls 9 CONTROL INSTALLATION 10 OPTIONAL MODULATION CONTINUOUS...

Page 3: ...ight side cover which can also be removed for ease of electrical connection For safety the door when closed keeps the side cover from being removed Single units have a plumbing compartment attached to...

Page 4: ...ral surface If any spacer material is used between the bracket and the structural material such as drywall increase fastener length accordingly In addition install a minimum of 2 field supplied fasten...

Page 5: ...stated in the STEAM LINE section on page 6 SGH Model Min Number of Blower Packs Min Overhead Clearance inches cm Min Front Clearance inches cm 010 1 18 45 30 76 020 1 18 45 36 91 050 1 36 91 84 213 1...

Page 6: ...8 9 The steam distributor mounting plate is perpendicular to the steam distributor When the mounting plate is attached to the side of the duct the distributor is level An upward or downward slope to...

Page 7: ...y and drain line connections should be installed in accordance with local plumbing codes WATER SUPPLY LINE 1 Humidifier is intended to operate on potable cold tap water 2 If the raw water is very hard...

Page 8: ...ediment and cause backup The drain line should be 1 O D copper pipe or larger Do not use plastic pipe for drain lines STEAM LINE 1 1 Steam lines for SGH models 010 through 020 require a minimum 7 8 O...

Page 9: ...nes for SGH 050 through 200 require 1 5 8 O D nominal 1 1 2 copper pipe For steam runs longer than 40 ft use insulated nominal 2 copper to ensure the draining of condensate 8 Do not use steel or plast...

Page 10: ...t for use when routing condensate hose back to humidifier s fill cup Similarly a short length of 3 8 I D condensate hose with clamps is supplied with Liebert s steam distributors to serve as a flexibl...

Page 11: ...ier if the blower pack gets overheated The control thermostat mounted on the steam distributor starts the fan when steam is generated 3 All blower packs have high efficiency blowers to minimize the fr...

Page 12: ...blower pack or air supply grille Do not mount on a outside wall where temperature fluctuation can affect control response 2 Mount duct humidistat in location representative of overall air humidity us...

Page 13: ...the humidifier starts its operation The controller waits 10 seconds before energizing the on board relays When the relays energize heating voltage is delivered to the cylinder After a 30 second delay...

Page 14: ...s a set of dry contacts at 61 20 on the control terminal strip The user can connect an indicator externally to 61 20 It will automatically be activated any time a fault is detected DOUBLE UNIT OPERATI...

Page 15: ...r implied by law No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the...

Page 16: ...___ Cylinder Last Replaced _________________________ MTH DAY YR _________________________ MTH DAY YR _________________________ MTH DAY YR PRINTED IN CANADA LIEBERT CORPORATION 1050 Dearborn Drive P O...

Reviews: