Liebert GXT2-10000RT208

User Manual–10kVA, 60 Hz, 120/208/240V

Summary of Contents for GXT2-10000RT208

Page 1: ...AC Power For Business Critical Continuity Liebert GXT2 10000RT208 User Manual 10kVA 60 Hz 120 208 240V...

Page 2: ......

Page 3: ...8 5 0 WHAT S INCLUDED 9 6 0 INSTALLATION AND CONFIGURATION 10 6 1 Install the Main Cabinet 10 6 1 1 Tower UPS Installation 10 6 1 2 Installing the Adjustable Rack Mount Kit Sold Separately 11 6 2 Ext...

Page 4: ...Tab 27 8 8 1 Low Battery Time Warning 27 8 8 2 Auto Battery Test Time 27 8 8 3 Battery Cabinets Number 27 8 8 4 Auto Battery Test 27 8 9 About Tab 28 9 0 CONTROLS AND INDICATORS 29 9 1 ON Alarm Silen...

Page 5: ...n on Battery 33 11 3 UPS Intelligent Communications 33 11 4 Remote Emergency Power Off 34 12 0 MAINTENANCE 35 12 1 Battery Replacement 35 12 1 1 Internal Battery Replacement Procedures 35 12 2 UPS Pow...

Page 6: ...tical and horizontal 29 Figure 10 REPO switch connections 34 Figure 11 UPS back panel control location 37 Figure 12 Power module replacement 37 TABLES Table 1 Electrical requirements 15 Table 2 DB 9 p...

Page 7: ...ants moisture flam mable liquids gases and corrosive substances This UPS contains no user serviceable parts except the internal battery pack The Off Bypass push button does not electrically isolate in...

Page 8: ...llowing precautions should be observed when working on batteries Remove watches rings and other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal pa...

Page 9: ...followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding co...

Page 10: ...ts output voltage whether utility power is present or not It supplies connected equip ment with clean sinewave power Sensitive electronic equipment operates best from sinewave power For ease of use th...

Page 11: ...istortion reflected on the utility is reduced This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT2 10000RT208 3 3 Inverter In normal...

Page 12: ...l battery cabinets are available to extend battery run times 3 7 Static Bypass The UPStation GXT2 10000RT208 provides an alternate path for utility power to the connected load in the unlikely event of...

Page 13: ...the battery access plate The cover plate can be removed by extracting the three screws at the top of the cover plate and lifting the plate off The two internal battery packs are compact assemblies re...

Page 14: ...convenience Figure 3 Hardwire terminal blocks Figure 4 Optional output distribution modules INPUT L1 N L2 N L1 L2 OUTPUT PD 101 Power Distribution Option with Internal Connector PD 102 Power Distribut...

Page 15: ...gram compact disk Ferrite beads 2 Box containing accessories is shipped in the UPS battery compartment UPStation GXT L1 L2 AC INPUT BATTERY UPS ON BYPASS GXT2U Configuration Program www liebert com Fo...

Page 16: ...208 may be installed either as a tower unit or in a rack depending on available space and use considerations Determine the type of installation and follow the appropriate instruc tions in either 6 1 1...

Page 17: ...bracket assembly 2 Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet 3 Install the rear member of each bracket assembly into rack enclosure wi...

Page 18: ...bers attached in Step 5 into the bracket assemblies by inserting the top and bottom edges of the inner members into the top and bottom curved tracks of the front members and sliding the equipment into...

Page 19: ...bly from tipping over One additional set of support base extensions ships with each external battery cabinet 4 Install the two battery packs and secure with the two brackets supplied 5 Connect the two...

Page 20: ...The input circuit breaker and the output cir cuit breaker on the rear fixed panel of the UPS disconnect all power between the main cabinet and the distribution box The manual bypass switch passes uti...

Page 21: ...48A 60A 6 AWG 4 AWG 17 6 in lb 2N m NOTE 1 The installer must provide circuit breaker protection according to local codes The utility disconnect should be within sight of the UPS or have an appropriat...

Page 22: ...odule to UPS 3 Snap together the electrical connectors on the UPS and on the output distribution 4 Use the screws removed in Step 2 to attach the output distribution to the rear of the UPS OUTPUT L1 O...

Page 23: ...of battery pack into the battery compartment and slide it in until the battery reaches the back of the UPS 5 Install the battery bracket on the front of the battery pack with two screws 6 Connect the...

Page 24: ...s 8 Using a voltmeter verify the expected L1 N L2 N and L1 L2 voltages a The bypass lamp by the switch will light b If the configuration program has been used to set the L N voltage at 100 110 or 115...

Page 25: ...blank access plate from the rear of the UPS 5 Connect the four position Anderson connector of the PD distribution into the mating connector inside the UPS 6 Using the same four screws attach the PD d...

Page 26: ...20 230 or 240 VAC respec tively If the measured L1 L2 voltage is equal to the average L N voltage times 1 73 then the phase angle is 120 degrees and the L N VAC may be set at either 120 or 127 VAC The...

Page 27: ...updated version 1 Use the Windows Explorer to find and open the Lbt_gxt2 1 6 exe installation program on the included software CD 2 When you see this PreSetup window select OK This will open the main...

Page 28: ...he error message below will be displayed The program must communicate with the UPS when it first opens when a new tab is opened and when the REFRESH APPLY or OK buttons are pressed If this message is...

Page 29: ...e UPS OFF Bypass button twice within four seconds hold the button one second each time This will disconnect all power to the load Changing any value or selecting deselecting any setting in the configu...

Page 30: ...data or contact closure If Auto Restart is enabled check mark in box the UPS will restart when input power is restored If the UPS turns off power to the load for any other reason manual restart is re...

Page 31: ...Inverter and Bypass The Options tab allows the behavior of the Any Mode Shutdown feature to be modified When the program opens or the REFRESH but ton is pressed the UPS setting is read by the configur...

Page 32: ...tab If version 1 6 or later is used with an earlier GXT 2U model with an earlier UPS firmware version the Any Mode Shutdown features cannot be changed If the configuration program is used with an ear...

Page 33: ...4 21 and 28 days 8 8 3 Battery Cabinets Number If additional batteries are attached to the UPS accurate battery runtime estimates are possible if the battery number and type of batteries are entered h...

Page 34: ...Configuration Program 28 8 9 About Tab The version number of the configuration program may be confirmed using the About Tab...

Page 35: ...er 24 hours retest the batteries After the batteries have been retested if only three of the five Battery indicators illuminate con tact your local dealer Liebert representative or Liebert Worldwide S...

Page 36: ...hould the battery fail this test the red Fault indicator along with the A and C diagnostic indicators will illuminate and an alarm will sound refer to 13 0 Troubleshooting The remote test feature func...

Page 37: ...s every 10 seconds This will change to two beeps every 5 seconds when the battery runs low approximately 2 minutes remaining but this is user configurable The AC Input indicator will extinguish and th...

Page 38: ...ead clamp to the network cable see illustration at right using the following directions 1 Open the ferrite bead 2 Place the network cable inside the ferrite bead groove 3 Wrap the cable once around th...

Page 39: ...r performing the 2 minute shutdown delay 11 3 UPS Intelligent Communications The UPStation GXT2 10000RT208 is equipped with an Intellislot port to provide advanced commu nication and monitoring option...

Page 40: ...ted equipment to comply with national and local wiring codes and regulations Figure 10 REPO switch connections CAUTION To maintain safety SELV barriers and electromagnetic compatibility signal cables...

Page 41: ...y and pull each out of the front of the UPS Be prepared to support the weight of the battery as it is withdrawn 5 Unpack the new battery assemblies taking care not to destroy the packing Compare new a...

Page 42: ...r grille with the screws securing them to the frame 7 Disconnect the slotted battery connectors from the internal battery packs 8 If additional external batteries are used disconnect the two external...

Page 43: ...S back panel control location Figure 12 Power module replacement Output Breaker 60A 250V T Input Breaker 60A 250V T Inverter Bypass Input Output UPStation GXT Power module pulled out of UPS Retaining...

Page 44: ...Indicators A C UPS failed battery test 2 second beep every 60 seconds Indicators A D L1 to L2 phase angle unacceptable Indicators B C REPO is currently activated UPS output cannot be started by any m...

Page 45: ...seconds more than 2 minutes of run time remaining Low Battery Two short beeps every 5 seconds less than 2 minutes of run time remaining On Bypass Reminder A one second beep every 2 minutes On Interna...

Page 46: ...dicator A are illuminated UPS internal fan has a problem or UPS shutdown due to temperature condition Load is on bypass power Ensure the UPS is not overloaded ventilation openings are not blocked and...

Page 47: ...or the Liebert Worldwide Support Group AC Input indicator is On diagnostic indicators A C and E are illuminated On Internal Bypass to notify user to move manual maintenance bypass switch to Bypass po...

Page 48: ...0 47 100 6 100 40 Internal Battery 1 External Battery Cabinet 10 251 Internal Battery 2 LRT Battery Pack 10 1030 20 118 20 538 30 74 30 332 40 52 40 269 50 39 50 231 60 32 60 195 70 26 70 158 80 22 80...

Page 49: ...tures The UPS will update the anticipated run time calculation only under certain conditions The UPS must have a steady load that is greater than 20 The UPS must be at 100 charge at the start of a bat...

Page 50: ...ed using configuration program L1 N L2 N Operating Voltage Range Without Battery Operation Except 100 VAC L N Operation 100 91 loading 100 VAC 140 VAC 90 71 loading 90 VAC 140 VAC 70 51 loading 80 VAC...

Page 51: ...specifications Model Number GXT2 288RTBKIT 2 Required DIMENSIONS W x D x H Shipping in mm 11 02 x 24 02 x 15 35 280 x 610 x 390 WEIGHT lb kg Unit 78 1 35 5 Shipping 83 6 38 Type Valve regulated non sp...

Page 52: ...0RT208 DIMENSIONS Rack Mount W x D x H Unit with bezel in mm 16 93 x 25 98 x 7 430 x 660 x 178 4U Shipping in mm 22 64 x 33 46 x 12 40 575 x 850 x 315 WEIGHT lb kg Unit 41 6 18 9 Shipping 50 6 23 BATT...

Page 53: ...s Model Number GXT2 10KPWR208 DIMENSIONS in mm Shipping W x D x H 22 04 x 28 14 x 9 88 560 x 715 x 251 WEIGHT lb kg Shipping 59 5 27 ENVIRONMENTAL Storage Temp 5 F to 122 F 15 C to 50 C Relative Humid...