Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169
EMAIL: [email protected] • Web Site: www.Liebert.com
82247 Rev 0
Liebert AC Power Low Exposure Transient Voltage Surge Suppressor,
electronic grade surge
protective device designed with sine wave tracking to protect electronic equipment and
microprocessor-based systems from transients on distribution panels, branch panels, or equipment in
low exposure locations. Dry contacts for remote indication standard.
AC Power Low Exposure TVSS Technical Specification
Connection Type
................................................. Parallel
Operating Voltage Range
................................... +/-15%
Fault Current Rating (AIC)
.................................. 14 kAIC
Dimensions
..................... .................................... 4.72”x4.72”x2.36”
Operating Frequency Range
............................. 47 – 63 Hz
Capacity
................................................................ Continuous
50 EMI/RFI Attenuation
................................... 40 dB
Response Time
.................................................... <0.5 ns
Dry Contract rating
.............................................. 125vac, 8.0A, 1.0pf
Operating Temperature
...................................... -40ºc to +50ºc
Operating Humidity
............................................. 0% to 95%
Status Indication
.................................................. LED, Dry Contacts
Certifications
........................................................ UL 1449, CUL, CE, ISO 9001
Warranty
............................................................... 5 Years
UL 1449
(second edition) Classification
120
volt
systems
.................................400 volts all modes
208 through 277 volt systems
..........800 volts all modes
480
volt
systems
.................................1,500 volts all modes
ORDERING INFORMATION
Building A Model Number: LPL 1 2 3
1: Nominal Voltage Requirements
2: System Configuration
3: Surge Current Capacity
Nominal Voltage Requirements
Model ID
System Configuration
Model ID
L-N
L-L
L-G
120 ........N/A....... 120
120
Single (2 Wire + Gnd)
N or L
120 .......208 ...... 120
120
Split (3 Wire + Gnd)
S
120 ........240....... 120
120
Wye (4 Wire + Gnd)
Y
N/A ........208....... 208
208
Delta Hi-Leg (4 Wire + Gnd)
H
230 ........400....... 230
230
Delta (3 Wire + Gnd)
D
N/A ........240....... 240
240
277 ........480....... 277
277
N/A ........400....... 400
400
N/A ........480....... 480
480
Surge Current Capacity
Model ID
100 kA/Phase
100
(L-N: 50 kA + L-G: 50 kA; N-G: 50 kA)
50 kA/Phase
50
(L-N: 25 kA + L-G: 25 kA; N-G: 25 kA)
PANEL I.D.
MODEL NUMBER(S)
25 kA/Phase
25 – 2
(L-N: 25 kA; N-G: 25 kA)
Job Name _______________________
Model # _________________________
Date ___________________________
Qty ____________________________
Quote # _________________________