–28–
3-way Valve
1. Pumping down
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
3-Way
valve
3-Way
valve
CLOSE
• Procedure
(1) Confirm that both liquid side and gas side
valves are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of
the 3-way valve.
– Connect the charge hose to the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the liquid side valve to the closed posi-
tion.
(6) Operate the air conditioner in cooling mode
and stop it when the gauge indicates
1kg/cm
2
g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm
2
g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valve ’s stem nuts and the ser-
vice port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Summary of Contents for TB-H488RSS5
Page 1: ...Ceiling Duct Type Air Conditioner SERVICE MANUAL MODELS TB H488RSS5 ...
Page 5: ...1 Specifications 1 1 Indoor unit 5 5 5 ...
Page 7: ...5 ...
Page 8: ...8 5 ...
Page 19: ... 19 Preparation of Piping 6 Connecting Pipes to the Indoor Unit ...
Page 20: ... 20 ...
Page 21: ... 21 ...
Page 39: ... 39 Electronic control device MAIN P C B ASM ...
Page 42: ......