Summary of Contents for PQCSB101S0

Page 1: ...NER Please read this manual carefully before operating your set and retain it for future reference P NO 3828A20467B www lg com TYPE Simple Central Controller MODEL PQCSB101S0 ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH РУССКИЙ ЯЗЫК ...

Page 2: ...wing 5 Name of each part 6 Operation tips 7 Individual operation 7 Total control for each group 7 Total On Off operation 7 Mode change 8 Setting individual lock 9 Setting total lock 9 Connected indoor unit search function 10 Self diagnosis for indoor unit 11 Set group inquiry 11 Function controller connection 12 ...

Page 3: ...Caution are to call the user s attention to the possible danger Read and follow them carefully in order to prevent a safety accident Warning and Caution are indicated in this guide and the product itself to help protect the users from danger WARNING CAUTION WARNING Entrust installation of the product to the service center because improper installation may cause fire an electric shock explosion and...

Page 4: ...k the service center for instruction It may cause fire or an electric shock unless you do that In use In use ˆ ł ˆ ˆ ł ˆ Service Center Make sure children or senor citizens use the product under proper observation in order to prevent safety accident Do not subject the product to shock It will cause product breakdown Do not pick the product with a sharp tool It may cause product breakdown with the ...

Page 5: ...ng with Function controller is connected as shown below PI 485 Central controller Function controller Individual controller Indoor unit 1 3 16 PQRCHCS0 FAN SPEED MODE Cooling Heating Auto Dry Fan Defrost Preheat Out door Slo Lo Med Hi Po Room Temp Total on Central Run SEARCH System Drawing Function controller and PI 485 are sold separately ...

Page 6: ...r Green No power Off During control Flickering 2 Power display LED On Off control of the connected indoor units 3 Individual On Off button total 16EA Sequentially turns off all indoor units connected to it 4 Total Off button Sequentially starts all indoor units connected to it 5 Total On button Central controller anchoring screws 4EA Owner Installation manual Actual name description sheet Addressi...

Page 7: ...n equivalent unit stops and LED is off Press Total On button then all units of that group operate sequently and LED is on Press Total Off button then each group units stop sequently and LED is off Total On Off Operation master slave combination 1 Press Total On button for more than 2sec then all linked units start sequentially and their LEDs turn on 2 Press Total Off button for more than 2sec then...

Page 8: ...is running in the cooling mode the status indicator LED would be green and when the indoor unit is running in the heating mode it will be orange This is applicable to heatpump models only Operating mode change for group of indoor units 1 Cooling operation of group of indoor units Press the Total On Total Off and no 5 button simultaneously to change all indoor units to cooling mode through the Cent...

Page 9: ...ton at the same time to cancel the lock function After lock function is canceled the equivalent LED of unlocked unit blinks for 5 sec Setting Total Lock for Each Group Setting total lock Press Total On Total Off and no 1 button at the same time All linked units are now controlled only by central controller control of main body is impossible After lock function is set LEDs of all locked units blink...

Page 10: ...n of the controller Indoor unit re search If all indoor units have not been searched during the automatic search press the Total On Total Off and no 16 button simultaneously to re search all the connected indoor units from no 1 to 16 by lighting up the LEDs in sequence Connected indoor unit indication Press the Total On Total Off and no 13 button simultaneously and all LEDs of the indoor units con...

Page 11: ...n If there is an error in the indoor unit the On Off status indicator LED of the that indoor unit turns red and when it recovers normal condition the LED will turn green or orange depending on the operating mode Press the Total On Total Off and no 6 button simultaneously The On Off status indicator LED equivalent to the group number set in the controller will flash e g If LED 2 blinks the group no...

Page 12: ...tton of the Central controller Then all the connected units will operate stop 2 Function controller indicates the operating statue of the first indoor unit of that group if no settings have been made at functional controller 3 However all indoors can also work under same running conditions as a group by making settings at the functional controller All Groups master slave Indoor Unit Control 1 Pres...

Page 13: ...tral controller for more than 3 seconds Now all the indoor units of slave group 1 will be turned on 2 Function controller of the selected slave controller displays the operating status of the first indoor unit It also displays Total on on its screen Now the setting can be done for whole group slave indoor units using function controller Indoor unit search 1 Select the search button of the function...

Page 14: ...Memo 14 Simple Central Controller ...

Page 15: ......

Reviews: