background image

4.0

Ton

 

Outdoor

 

Unit

Performance:

Cooling

 

Mode:

Capacity

 

(Btu/h)

48,000

Capacity

 

(tons)

4.0

Power

 

Input

 

(kW)

5.1

EER

9.50

Heating

 

Mode:

Power

 

Input

 

(kW)

5.3

Cooling

 

Nominal

 

Test

 

Conditions:

Heating

 

Nominal

 

Test

 

Conditions:

Indoor:

80

˚

F

 

DB

 

/67

˚

F

 

WB

Outdoor:

95

˚

 

DB

Indoor:

70

˚

F

 

DB

Outdoor:

47

˚

F

 

DB

 

/43

˚

F

 

WB

Electrical:

Power

 

Supply

 

(V/Hz/Ph)

208

230/60/1

MOP

 

(A)

55

MCA

 

(A)

33

Rated

 

Amps

 

(A)

25.8

Compressor

 

(A)

24.8

Fan

 

Motor

 

(A)

1.0

Max

 

Starting

 

Current

 

(A)

Operating

 

Range:

Cooling

 

(

˚

F

 

DB)

23

 ‐ 

118

Heating

 

(

˚

F

 

WB)

4

 ‐ 

60

Notes:

Unit

 

Data:

Refrigerant

 

Type

R410A

Refrigerant

 

Control

EEV

Net

 

Unit

 

Weight

 

(lbs)

234

Heat

 

Exchanger

 

Coating

GoldFin™

Compressor:

Fan:

Quantity

2

Air

 

Flow

 

Rate

 

(CFM)

3,885

Piping:

Refrigerant:

Refrigerant

 

Charge

 

(lbs)

6.6

Standard

 

Features:

 

Limited

 

Warranty

 

with

 

LG

 

Certified

 

Installation

     

 

Two

 

Year

 

Functional

 

Parts

 

Warranty

     

 

Additional

 

Four

 

Year

 

Compressor

 

Warranty

 

Night

 

Quiet

 

Operation

 

Fault

 

Detect

 

and

 

Diagnosis

LG

 

Electronics

 

USA,

 

Inc.

 

1000

 

Sylvan

 

Ave,

 

Englewood

 

Cliffs,

 

NJ

 

07632/www.lg.com/us/

For

 

continual

 

product

 

development,

 

LG

 

reserves

 

the

 

right

 

to

 

change

 

specifications

 

without

 

notice.

Page

 

1

 

of

 

2

SEER

15.20

Vapor

 

Line

 

(in,

 

OD)

5/8

 

Braze

VRF

SB

BB

002

US

    

011D21

 

1.The

 

combina on

 

ra o

 

must

 

be

 

between

 

50

130%.

 

2.Sound

 

pressure

 

levels

 

are

 

tested

 

in

 

an

 

anechoic

 

chamber

 

under

 

Korea

 

Standard

 

KSA0701.

 

3.All

 

communica on

 

cable

 

to

 

be

 

minimum

 

18

 

AWG,

 

2

conductor,

 

stranded,

 

shielded

 

and

 

must

 

comply

 

with

 

applicable

 

local

 

and

 

national

 

code.

 

4.All

 

communica on

 

cable

 

to

 

be

 

minimum

 

18

 

AWG,

 

2

conductor,

 

stranded

 

and

 

must

 

comply

 

with

 

applicable

 

local

 

and

 

national

 

code.

 

5.The

 

data

 

men oned

 

in

 

the

 

above

 

tables

 

is

 

applied

 

with

 

non

ducted

 

indoor

 

units.

 

6.This

 

data

 

is

 

rated

 

0

   

above

 

sea

 

level,

 

with

 

25

   

of

 

refrigerant

 

line

 

per

 

indoor

 

unit

 

and

 

a

 

0

   

level

 

difference

 

between

 

outdoor

 

and

 

indoor

 

units.

  

All

 

capacities

 

are

 

net

 

with

 

a

 

combination

 

ratio

 

between

 

95

 

 

105%.

 

7.The

 

voltage

 

tolerance

 

is

 

±

 

10%.

 

8.Power

 

wiring

 

cable

 

size

 

must

 

comply

 

with

 

the

 

applicable

 

local

 

and

 

na onal

 

code.

 

9.Must

 

follow

 

installa on

 

instruc ons

 

in

 

the

 

applicable

 

LG

 

installa on

 

manual.

Capacity

 

(Btu/h)

 

53,500

Date:

Job

 

Name/Location:

PO

 

No.:

Architect:

Engr:

GC:

Rep:

For:

File

Approval

Mech:

Resubmit

Other

(Company)

(Project

 

Manager)

Tag

 

#:

ARUN047GS2

Multi

 

V™

 

Mini

Inverter

 

Rotary

 

Quantity

1

Oil

 

/

 

Type

PVE/FV50S

Type

Propeller

Fan

 

Motor/Drive

Brushless

 

Digitally

 

Controlled/Direct

Liquid

 

Line

 

(in,

 

OD)

3/8

 

Braze

Communication

 

Cable

 

(No.

 

x

 

AWG)

HSPF

9.20

Max

 

Num

 

of

 

Indoor

 

Units¹

8

Sound

 

Pressure²

  

dB(A)

 

(CLG/HTG)

51/53

Outdoor

 

to

 

Indoor³

2

 

x

 

18

Outdoor

 

to

 

Outdoor

2

 

x

 

18

Shipping

 

Weight

 

(lbs)

258

Reviews: