76
TEST RUN
ENGLISH
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1” ~ “op4” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Target pressure is set
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“HEAT” , “COOL” Push the ‘
●
’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
“Heat”
“Cool”
op1
Increase capacity
Increase capacity
-3°C(26.6°F)
+2°C(35.6°F)
op2
Decrease power consumption
Increase capacity
-1.5°C(29.3°F)
-2°C(28.4°F)
op3
Decrease power consumption Decrease power consu2.5°C(36.5°F)
-4°C(24.8°F)
op4
Decrease power consumption Decrease power consumption -4.5°C(23.9°F)
-6°C(21.2°F)
Target pressure adjusting
mode setting method