3 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN31
Ⓕ
: Connection branch pipe between Outdoor
units: ARCNN21
10m
(33ft)
or less
H 110m(36
1ft)
40m(131ft)
L 200m(656ft)
40m(131ft)
Master
Slave2
Slave1
ODU Capacity
Master ≥ Slave1 ≥ Slave2
Branch pipe can not be used after header
Total pipe length = A+a+b+c+d+e+f
≤
1000m(3281ft)
L
Longest pipe length
*Equivalent pipe length
A+f
≤
200m(656ft)
A+f
≤
225m(738ft)
l
Longest pipe length after 1st branch
f
≤
40m(131ft)
H
Difference in height (Outdoor Unit
÷
Indoor Unit)
H
≤
110m(361ft)
h
Difference in height (Indoor Unit
÷
Indoor Unit)
h
≤
40m(131ft)
h1
Difference in height (Outdoor Unit
÷
Outdoor Unit)
h1
≤
5m(16ft)
32
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH