CORRECTION FACTORS | 159
Correction Factors
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Heating Correction Factor for 072BTE5 / 072DTE5 to 336BTE5 / 336DTE5 models is 1.0 for all equivalent lengths and elevation differences.
Elevation Correction Factors
For each outdoor unit, calculate the equivalent length of the liquid line from the outdoor unit to the farthest indoor unit. Also, determine the
elevation difference of farthest indoor unit above or below the outdoor unit. Find corresponding cooling capacity correction factor in tables
below and on the next page. Multiply the cooling correction factor by standard cooling capacity. The resultant is the NET cooling capacity.
Repeat for heating correction factor.
Equivalent Length (ELF)
1
Elevation
Differences
(ft.)
25
33
66
98 131 164 197 230 262 295 328 361 394 427 459 492 525 558 591 623 656 689 738
HU—Indoor units above heat pump unit (ft.)
0
1.0 0.99 0.98 0.96 0.95 0.94 0.93 0.92 0.92 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.83 0.82
25
0.99 0.99 0.98 0.97 0.95 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.83 0.82
33
-
0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.83 0.82
66
-
-
0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.83 0.82
98
-
-
-
0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.89 0.88 0.87 0.86 0.86 0.85 0.85 0.84 0.83 0.83 0.82
131
-
-
-
-
0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.83 0.83 0.82
164
-
-
-
-
-
0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.83 0.83 0.82
197
-
-
-
-
-
-
0.94 0.93 0.92 0.91 0.90 0.89 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.84 0.83 0.82
230
-
-
-
-
-
-
-
0.93 0.92 0.91 0.90 0.90 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.84 0.83 0.82
262
-
-
-
-
-
-
-
-
0.92 0.91 0.90 0.90 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.84 0.83 0.82
295
-
-
-
-
-
-
-
-
-
0.91 0.90 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.82
328
-
-
-
-
-
-
-
-
-
-
0.91 0.90 0.89 0.88 0.88 0.88 0.86 0.86 0.85 0.84 0.84 0.83 0.82
361
-
-
-
-
-
-
-
-
-
-
-
0.90 0.89 0.88 0.88 0.88 0.86 0.86 0.85 0.84 0.84 0.83 0.82
HL—Indoor units below heat pump unit (ft.)
0
1.0 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.82
25
1.0 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.82
33
-
0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.82
66
-
-
0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.82
98
-
-
-
0.97 0.96 0.95 0.94 0.93 0.92 0.92 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.85 0.84 0.83 0.83
131
-
-
-
-
0.96 0.95 0.94 0.93 0.92 0.92 0.91 0.90 0.89 0.89 0.88 0.87 0.86 0.86 0.85 0.85 0.84 0.83 0.83
164
-
-
-
-
-
0.95 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.83 0.83
197
-
-
-
-
-
-
0.94 0.94 0.93 0.92 0.91 0.90 0.89 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.84 0.83
230
-
-
-
-
-
-
-
0.94 0.93 0.92 0.91 0.90 0.90 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.84 0.83
263
-
-
-
-
-
-
-
-
0.93 0.92 0.91 0.90 0.90 0.89 0.88 0.87 0.87 0.86 0.85 0.85 0.84 0.84 0.83
295
-
-
-
-
-
-
-
-
-
0.92 0.91 0.90 0.90 0.89 0.88 0.87 0.87 0.86 0.86 0.85 0.84 0.84 0.83
328
-
-
-
-
-
-
-
-
-
-
0.91 0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83
361
-
-
-
-
-
-
-
-
-
-
-
0.91 0.90 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83
Table 3: ARUM Outdoor Unit Cooling Correction Factors (072BTE5 / 072DTE5 to 336BTE5 / 336DTE5).
1
ELF = Equivalent Pipe Length in Feet—Sum of the actual pipe length plus allocations for pressure drop through elbows, valves, and other fittings in equivalent length.
CORRECTION FACTORS
The correction factors shown below are calculated in the LATS software programs.