15. Power relay control
• Power relay turns on 1 second later after the power is input to the outdoor unit.
• Control sequence : power on
➔
PTC operating
➔
power relay on
16. Protection from total current control
■
CT1 control
• If the operating current reaches I1, the operating frequency of the compressor decrease.
• After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
■
CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.
-22-
❇
I1:Current of operating frequency down
I2: Current of compressor cut off
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Control table
17. Protection from DC Peak Current
■
DC Peak Current Error by a fault signal of IPM
• If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
• If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6.
■
DC Peak Current Error by the compressor lock
• If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the
appliance turns off and display ERROR CODE 6.
■
DC Peak Current Error by the Outdoor Fan Lock
• If it’s 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is
operating, the appliance turns off and display ERROR CODE 6.
Summary of Contents for LS-J0762NM
Page 66: ...Schematic Diagram 66 Indoor _YL _UL Series ...
Page 67: ... 67 Indoor _NM _NN Series ...
Page 68: ... 68 Outdoor 7K AC Series ...
Page 69: ... 69 Outdoor 12K AC Series ...
Page 70: ... 70 Outdoor 9K DC Series ...
Page 73: ... 73 Outdoor 12K DC Series ...
Page 80: ...Memo 80 ...
Page 81: ... 81 Memo ...
Page 82: ...P No 3828A20061S February 2003 Printed in Korea ...