background image

Date:

Job

 

Name/Location:

PO

 

No.:

Architect:

Engr:

GC:

Rep:

For:

File

Approval

Mech:

Resubmit

Other

(Company)

(Project

 

Manager)

Tag

 

#:

ARNU183TQC2

Multi

 

V™

 

4

Way

 

Ceiling

 

Cassette

Performance:

Cooling

 

Nominal

 

Test

 

Conditions:

Heating

 

Nominal

 

Test

 

Conditions:

Indoor:

80°F

 

DB/67°F

 

WB

Outdoor
:

95°F

 

DB

Indoor:

70°F

 

DB

Outdoor
:

47°F

 

DB/43°F

 

WB

Heating

 

Capacity

 

(Btu/h)

 

21,500

Electrical:

Power

 

Supply

  

(V/Hz/Ø)

208

230/60/1

Rated

 

Amps

 

(A)

 

0.2

Piping:

Refrigerant:

Liquid

 

Line

 

(in,

 

OD)

1/4

 

Flare

Vapor

 

Line

 

(in,

 

OD)

1/2

 

Flare

Condensate:

Standard

 

Features:

 

•Limited

 

Warranty

 

with

 

LG

 

Cer

fi

ed

 

Installa on

     

•Two

 

Year

 

Functional

 

Parts

 

Warranty

•Corner

 

Access

 

Panels

Controls

 

Features:

Fan:

Type

Turbo

Quantity

1

Motor/Drive

Brushless

 

Digitally

 

Controlled/Direct

Airflow

 

Rate

 

H/M/L

 

(CFM)

396/388/353

Optional

 

Accessories:

Notes:

 

1.The

 

Power

 

Input

 

is

 

rated

 

at

 

high

 

speed.

 

2.Maximum

 

li

 

is

 

27

 

in

 

from

 

bo om

 

of

 

unit.

 

3.See

 

Engineering

 

Manual

 

for

 

sensible

 

and

 

latent

 

capaci es.

 

4.Sound

 

Pressure

 

levels

 

are

 

tested

 

in

 

an

 

anechoic

 

chamber

 

under

 

ISO

 

Standard

 

1996.

 

5.All

 

communica on

 

cable

 

to

 

be

 

minimum

 

18

 

AWG,

 

2

conductor,

 

stranded,

 

shielded

 

and

 

must

 

comply

 

with

 

applicable

 

local

 

and

 

national

 

code.

 

6.Power

 

wiring

 

cable

 

size

 

must

 

comply

 

with

 

the

 

applicable

 

local

 

and

 

na onal

 

code.

 

7.This

 

unit

 

comes

 

with

 

a

 

dry

 

nitrogen

 

charge.

 

8.This

 

data

 

is

 

rated

 

0

   

above

 

sea

 

level,

 

with

 

25

   

of

 

refrigerant

 

line

 

per

 

indoor

 

unit

 

and

 

a

 

0

   

level

 

difference

 

between

 

outdoor

 

and

 

indoor

 

units.

  

All

 

capacities

 

are

 

net

 

with

 

a

 

combination

 

ratio

 

between

 

95

 

 

105%.

 

9.Must

 

follow

 

installa on

 

instruc ons

 

in

 

the

 

applicable

 

LG

 

installa on

 

manual.

Required

 

Accessories:

Grille

 

Kit

 

(PT

UQC)

Page

 

1

 

of

 

2

VRF

SB

DE

005

US

   

011H03

Unit

 

Data:

Refrigerant

 

Type

R410A

Refrigerant

 

Control

EEV

Net

 

Unit

 

Weight

 

(lbs)

35

Shipping

 

Weight

 

(lbs)

42

Primary

 

Filter

Washable

 

Pre

filter

Secondary

 

Filter

Plasma

Entering

 

Mixed

 

Air:

Heating

 

Min

 

(°F

 

DB)

59

Grille

 

Weight

 

(lbs)

5.5

Condensate

 

Line

 

(in,

 

OD)

1

Power

 

Input¹

 

(W)

30

Wireless

 

Handheld

 

Remote

 

Controller

 

(PQWRHDF0)

7

Day

 

Programmable

 

Controller

 

(PQRCUSA)

Simple

 

Controller

 

with

 

Mode

 

(PQRCUCS0C)

Simple

 

Controller

 

without

 

Mode

 

(PQRCFCS0C)

Dry

 

Contact

 

Unit

 

(PQDSB1,

 

PQDSBC)

Factory

 

Installed

 

Pump²

Yes

Ventilation

 

Kit

 

(PTVK430)

19,100

Cooling

 

Max³

 

(°F

 

WB)

76

Sound

 

Pressure

⁴ 

dB(A)

 

(H/M/L)

37/35/34

Btu/h

 

Indoor

 

Unit

Total

 

Cooling

 

Capacity

 

(Btu/h)

19,100

Wall

 

Mounted

 

Temperature

 

Sensor

 

(PQRSTA0)

Grille

 

Shipping

 

Weight

 

(lbs)

8

LG

 

Electronics

 

USA,

 

Inc.

 

1000

 

Sylvan

 

Ave,

 

Englewood

 

Cliffs,

 

NJ

 

07632/www.lg

vrf.com

For

 

continual

 

product

 

development,

 

LG

 

reserves

 

the

 

right

 

to

 

change

 

specifications

 

without

 

notice.

 

•Auto

 

changeover

  

(Heat

 

Recovery

 

Only)

 

•Auto

 

opera on

 

•Auto

 

restart

 

•Child

 

lock

 

•Dual

 

thermistor

 

control

 

•Forced

 

opera on

 

•Group

 

control

 

•High

 

ceiling

 

•Hot

 

start

 

•Self

 

diagnos cs

 

•Sleep

 

mode

 

•Timer

 

(on/o

)

 

•Weekly

 

schedule

 

•So

 

dry

 

(dehumidi

fi

ca on)

 

•Auto

 

direc on/swing

 

(up/down)

 

•Fan

 

speed

 

control

 

•Chaos

 

wind

 

(random

 

fan

 

speed)

 

•Swirl

 

wind

 

(alterna ng

 

vanes)

 

•Jet

 

cool

 

(fast

 

cooling)

Reviews: