24
Multi V Ducted Indoor Units
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Electrical
−
Low-Static Ducted L1/L2/L3 Chassis
Table 12: Low-Static Ducted L1/L2/L3 Chassis Electrical Data.
Model
Voltage Range
MCA
MOP
Rated Amps (A)
Power Supply
Power Input (W)
Hz
Volts
Phase
Cooling
Heating
L1 Units
ARNU073L1G4
208-230
0.5
15
0.4
60
208-230
1
40
40
ARNU093L1G4
0.5
0.4
40
40
L2 Units
ARNU123L2G4
208-230
1.0
15
0.76
60
208-230
1
85
85
ARNU153L2G4
1.0
0.76
85
85
ARNU183L2G4
1.0
0.76
85
85
L3 Units
ARNU243L3G4
208-230
1.2
15
0.97
60
208-230
1
115
115
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.
Table 13: Vertical Air Handler NJ/NK Chassis Electrical Data.
Model
Voltage Range
MCA
MOP
Rated Amps (A)
Power Supply
Power Input (W)
Hz
Volts
Phase
Cooling
Heating
NJ Units
ARNU123NJA4
208-230
1.4
15
1.12
60
208-230
1
228
228
ARNU183NJA4
1.4
1.12
228
228
ARNU243NJA4
1.4
1.12
228
228
ARNU303NJA4
1.4
1.12
228
228
ARNU363NJA4
1.4
1.12
228
228
NK Units
ARNU423NKA4
208-230
2.3
15
1.8
60
208-230
1
366
366
ARNU483NKA4
2.3
1.8
366
366
ARNU543NKA4
2.3
1.8
366
366
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.