1. Specification
Indoor
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Conversion Formula
kW = Btu/h x 0.0002931
cfm = CMM x 35.3
Power Supply
Ø / V / Hz
Capacity(*)
Btu/h Class
Current
Running Current
A
Fan
Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate
CMM
(H / M / L)
CFM
External Static Pressure
mmAq
Capacitor
μF / Vac
Drive
Coil
Row x Column x FPI
Dimensions Body
mm
(W x H x D)
inch
Decorative Panel
mm
inch
Net Weight
Body
kg (lbs)
Decorative Panel
kg (lbs)
Air Filter
Sound Level (H / M / L)
dB(A)+3
Piping
Liquid
mm (inch)
Connections
Gas
mm (inch)
Drain(OD/ID)
mm (inch)
Dehumidification Rate
l/h
Safety Devices
Temperature Sensor
Refrigerant
Refrigerant Control
Transmission Interunit Cable
No. x AWG
Model
AMNW18GDCL0 [LMAN186HV]
1/208-230/60
18,000
0.28
BLDC
Cross Flow Fan
20x1
12/10/8.2
247/230/212
-
-
Direct Drive
3R x 18C x 22
1030 x 325 x 250
40-9/16 x 12-25/32 x 9-27/32
-
-
11(24.5)
-
Long Life Filter
37/33/28
6.35 (1/4)
12.7 (1/2)
21.5/16 (0.846/0.630)
1.9
Fuse, Thermal Protector for Fan Motor
Thermistor
R410A
EEV(in Outdoor unit or BD)
4×18(including earth)