Part 4 Trouble Shooting
- 76 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Display
code
Title
Cause of error
Check point & Normal condition
32
High temperature in
Discharge pipe of the
inverter compressor
• Overload operation
(Outdoor fan constraint,
screened, blocked)
• Refrigerant leakage
(insufficient)
• Poor INV Comp
Discharge sensor
• LEV connector displaced
/ poor LEV assembly
• Check outdoor fan constraint/ screened/ flow
structure
• Check refrigerant leakage
• Check if the sensor is normal
• Check the status of EEV assembly
CN_TH3
(RED 4Pin Connector)
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.