Part 4 Trouble Shooting
- 56 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
6.7 Troubleshooting Outdoor Error
▶
A2UW14GFA0 / A2UW16GFA0 / A3UW18GFA0 / A3UW21GFA0
Display
code
Title
Cause of error
Check point & Normal condition
21
High current into the
compressor
• Compressor blocked
• Disconnection/shortcircuit
inside compressor
• Over load operation
(Outdoor fan constraint,
screened, blocked)
• Burned parts inside PCB
• Check compressor constraint
• Check compressor wire open/short
• Check compressor insulation damage
• Check outdoor fan constraint / screened / flow
structure
• Check if IPM burned
Summary of Contents for ABNQ18GHLA0