background image

INSTALLATION MANUAL

AIR

CONDITIONER

www.lg.com

Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards
by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.

Ceilling Concealed Duct
Original instruction

Copyright © 2018 LG Electronics Inc. All Rights Reserved.

ENGLISH

BAHASA INDONESIA

Rev. : 01(11T18)

*MFL67448535*

Summary of Contents for ABNQ09GL1A2

Page 1: ... work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly Ceilling Concealed Duct Original instruction Copyright 2018 LG Electronics Inc All Rights Reserved ENGLISH BAHASA INDONESIA Rev 01 11T18 MFL67448535 ...

Page 2: ...conditioner is used for many hours Clean the air filter once every 2 weeks Dust and impurities collected in the air filter may block the air flow or weaken the cooling dehumidifying functions For your records Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes Write the model number and the serial number here Model number Serial number You ca...

Page 3: ...llation agency Otherwise it may cause a fire electrical shock explosion or injury Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not attached securely it could result in a fire or electric shock due to dust water etc Always install an air leakage bre...

Page 4: ... the power cord Otherwise it may cause a fire or electrical shock When the product is submerged into water always contact the service center Otherwise it may cause a fire or electrical shock Take care so that children may not step on the outdoor unit Otherwise children may be seriously injured due to falling down CAUTION Installation Install the drain hose to ensure that drain can be securely done...

Page 5: ...red remote controller installation 16 OPTIONAL OPERATION 16 Installer Setting Test Run Mode 17 Installer Setting Setting Address of Central Control 18 Installer Setting Thermistor 19 Installer Setting Group Setting 20 Installer Setting Dry Contact Mode Setting 21 Installer Setting Celsius Fahrenheit Switching 22 Installer Setting Optional Function Setting 23 Installer Setting Remote controller Mod...

Page 6: ...6 ENGLISH INTRODUCTION INTRODUCTION Air outlet vents Air filters Control box Air intake vents Wired Remote Controller ...

Page 7: ...y an electrical noise The place where air circulation in the room will be good There should not be any heat source or steam near the unit Suitable dimension H is necessary to get a slope to drain as shown in the figure Confirm the positional relationship between the unit and suspension bolts Installation the ceiling opening to clean the filter or service under the product Top view Unit mm inch Sid...

Page 8: ...ole side as a figure for easy water drainage Position of console Bolt A place where the unit will be leveled and that can support the weight of the unit A place where the unit can withstand its vibration A place where service can be easily performed CASE 2 Dimension Capacity kBtu h A B C D E F G H I J 9 733 772 628 700 36 190 20 660 155 700 12 18 933 972 628 700 36 190 20 860 155 900 24 1133 1172 ...

Page 9: ... bolts for locking the suspension bolts on the ceiling Mount the suspension bolts to the set anchor firmly Secure the installation plates onto the suspension bolts adjust level roughly using nuts washers and spring washers 1 Set anchor Old building New building 2 Plate washer 3 Spring washer 4 Nut 5 Suspension bolts CAUTION The Power cord connected to the unit should be selected according to the f...

Page 10: ...of suction from bottom size bend the Panel rear and screw with cabinet case Air outlet Air Filter Panel Rear Air outlet Air Filter Panel Rear Air outlet Air Filter Panel Rear Ceiling Ceiling 1 100 1 50 Drainage hole CORRECT INCORRECT Drainage hole Caution for gradient of unit and drain piping Lay the drain hose with a downward inclination so water will drain out Always lay the drain with downward ...

Page 11: ...o provide up and down slope to prevent reversal flow During drain piping connection be careful not to exert extra force on the drain port on the indoor unit The outside diameter of the drain connection on the indoor unit is 32 mm Piping material Polyvinyl chloride pipe VP 25 and pipe fittings Be sure to execute heat insulation on the drain piping Install the drain raising pipes at a right angle to...

Page 12: ... has an excellent heat resistance over 120 C 2 Precautions in high humidity circumstance This air conditioner has been tested according to the KS Standard Conditions with Mist and confirmed that there is not any default However if it is operated for a long time in high humid atmosphere dew point temperature more than 23 C water drops are liable to fall In this case add heat insulation material acc...

Page 13: ... Install the product so as not to make a gap with the wall side and to prevent shaking after the installation Can set up Wired remote controller cable into three directions Setup direction the surface of wall reclamation upper right If setting up remote controller cable into upper and right side please set up after removing remote controller cable guide groove Remove guide groove with long nose Re...

Page 14: ...ot to damage the inside components when separating Please connect indoor unit and remote controller using connection cable Please use extension cable if the distance between wired remote controller and indoor unit is more than 10m Wall Side Wall Side Wall Side Wall Side Connecting order Separating order Please check if connector is normally connected Connecting cable Indoor Unit side CAUTION When ...

Page 15: ...ion at an average temperature Do not install the remote controller where it can be affected by Drafts or dead spots behind doors and in corners Hot or cold air from ducts Radiant heat from sun or appliances Concealed pipes and chimneys Uncontrolled areas such as an outside wall behind the remote controller This remote controller is equipped with a seven segment LED display For proper display of th...

Page 16: ...ion temperature up down wind flow control wind direction start stop button 4 If pressing button long for 3 seconds it enters into remote controller setter setup mode If pressing once shortly it enters into user setup mode Please press more than 3 seconds for sure Please cancel the right and left of wind direction for RAC product 1 Setup figure 01 blinks at the lower part of indication window 2 Fun...

Page 17: ...on to save 6 Pressing button will exit settings mode After setup it automatically gets out of setup mode if there is no button input for 25 seconds When exiting without pressing set button the manipulated value is not reflected 7 If entering into address setup mode by using button it indicates as picture below 2 If pressing button long for 3 seconds it enters into remote controller setter setup mo...

Page 18: ...ngs mode After setup it automatically gets out of setup mode if there is no button input for 25 seconds When exiting without pressing set button the manipulated value is not reflected Thermistor Table Temperature sensor selection Function 01 Remote controller Operation in remote controller temperature sensor 02 Indoor unit Operation in indoor unit temperature sensor 03 2TH Cooling Operation of hig...

Page 19: ... gets out of setup mode if there is no button input for 25 seconds When exiting without pressing set button the manipulated value is not reflected 1 If pressing button repeatedly it moves to master slave selection menu as picture below 2 5 Refer to the group control part for details When controlling in groups basic operation settings airflow strength weak medium strong lock setting of the remote c...

Page 20: ...ct mode setup menu as picture below 2 Pressing button will exit settings mode After setup it automatically gets out of setup mode if there is no button input for 25 seconds When exiting without pressing set button the manipulated value is not reflected 5 Installer Setting Dry Contact Mode Setting Dry contact function is the function that is possible to use only when dry contact equipment is separa...

Page 21: ...oller setter setup mode If pressing once shortly it enters into user setup mode Please press more than 3 seconds for sure 1 Press button to exit or system will automatically exit after 25 seconds without any input 5 Repeat pressing button to select Function code 12 Ex Fahrenheit Setting 2 Select Temperature unit mode by pressing button 00 Celsius 01 Fahrenheit 3 Press button to save or release 4 W...

Page 22: ... for 3 seconds it enters into remote controller setter setup mode If pressing once shortly it enters into user setup mode Please press more than 3 seconds for sure 1 If pressing button repeatedly it moves to the selected option function code as picture below 2 Pressing button will exit settings mode After setup it automatically gets out of setup mode if there is no button input for 25 seconds When...

Page 23: ...ting mode only Press and hold button for more than 3 seconds to enter the installer settings mode 1 Press button to exit 5 Move to the installer code number 42 in the menu using button 2 Select the remote control master slave using button 3 Press button to save the setting 4 Code value for mode lock setting Set value h It can limit only wired remote controller button other controllers can change o...

Page 24: ...setup mode by using button it indicates as the picture below 2 Select ESP fan step by pressing button 01 very low 02 low 03 medium 04 high 05 power 3 Move to ESP value setting by pressing button It is 000 when delivering from the warehouse 4 Press button to setup ESP value It is possible to setup ESP value from 1 to 255 and 1 is the smallest and 255 is the biggest 5 Function code ESP code ESP valu...

Page 25: ...pecific range belongs to the product Function code ESP code ESP value Press button to save 7 Select ESP fan step again by using button and setup ESP value as No 4 and 5 that corresponds each wind flow 6 Press button to exit After setup it automatically gets out of setup mode if there is no button input for 25 seconds When exiting without pressing set button the manipulated value is not reflected 8...

Page 26: ...onds the system will be entered into the installer setting mode After entering into the installer setting mode select the static pressure step setting code value by pressing the button Static pressure step setting code value 32 1 Select the desired setting value with the temperature up ƞ down Ơ button 2 When pressing button currently established static pressure value will be set up 3 When pressing...

Page 27: ...08 117 124 131 Model Step CMM Static Pressure mmAq Pa 0 0 1 10 2 20 3 29 4 39 5 49 Setting Value 32 01 32 02 32 03 32 04 32 05 32 06 AMNW12GL2A2 AMNQ12GL2A0 ABNQ12GL2A2 LOW 7 78 82 87 93 100 107 MID 8 5 87 91 94 100 108 116 HIGH 10 96 100 103 109 117 125 Model Step CMM Static Pressure mmAq Pa 0 0 1 10 2 20 3 29 4 39 5 49 Setting Value 32 01 32 02 32 03 32 04 32 05 32 06 AMNW18GL2A2 AMNQ18GL2A0 ABN...

Page 28: ...f Setting On Default SW3 Group Control Selection of Master or Slave Master Slave Off SW4 Dry Contact Mode Selection of Dry Contact Mode Wired Wireless remote controller Selection of Manual or Auto operation Mode Auto Off SW5 Installation Fan continuous operation Continuous operation Removal Working Off ...

Page 29: ...ENGLISH 29 ...

Page 30: ......

Page 31: ...roduk Pekerjaan pemasangan harus dilakukan sesuai dengan standar pengabelan nasional oleh petugas resmi saja Silakan simpan buku panduan pemasangan ini untuk referensi di masa mendatang setelah membaca seluruhnya Ceiling Concealed Duct Petunjuk asli BAHASA INDONESIA Hak cipta 2018 LG Electronics Semua hak cipta di lindungi ...

Page 32: ...a pendingin ruangan digunakan selama berjam jam Bersihkan filter udara setiap 2 minggu sekali Debu dan kotoran yang terkumpul di filter udara dapat menghambat aliran udara atau melemahkan fungsi pendinginan pengurang kelembapan Untuk catatan Anda Rekatkan tanda terima Anda dengan halaman ini apabila Anda membutuhkannya untuk membuktikan tanggal pembelian atau untuk garansi Tuliskan nomor model dan...

Page 33: ...atan listrik Untuk pemasangan produk selalu hubungi pusat layanan atau agen pemasangan profesional Jika tidak itu dapat menyebabkan kebakaran sengatan listrik ledakan atau cedera Pasang penutup komponen listrik ke unit dalam ruangan dan panel servis ke unit luar ruangan dengan erat Jika penutup komponen listrik unit dan panel servis unit luar ruangan tidak dipasang dengan erat itu dapat menyebabka...

Page 34: ...uh benda apa pun di atasnya Itu dapat menyebabkan cedera akibat jatuhnya unit atau benda tersebut Jangan menaruh benda yang berat di atas kabel daya Jika tidak itu dapat menyebabkan kebakaran atau sengatan listrik Saat produk terendam air selalu hubungi pusat layanan Jika tidak itu dapat menyebabkan kebakaran atau sengatan listrik Berhati hatilah agar anak anak tidak menginjak unit luar ruangan Ji...

Page 35: ...ak jauh berkabel 16 OPERASI OPSIONAL 16 Pengaturan Pemasang Mode Uji Coba 17 Pengaturan Pemasang Mengatur Alamat Kontrol Pusat 18 Pengaturan Pemasang Termistor 19 Pengaturan Pemasang Pengaturan Kelompok 20 Pengaturan Pemasang Pengaturan Mode Kontak Kering 21 Pengaturan Pemasang Mengganti Celsius Fahrenheit 22 Pengaturan Pemasang Pengaturan Fungsi Opsional 23 Pengaturan Pemasang Kunci Mode Pengenda...

Page 36: ...6 BAHASA INDONESIA PENDAHULUAN PENDAHULUAN Lubang keluar udara Filter udara Kotak kontrol Lubang masukan udara Pengendali Jarak Jauh Berkabel ...

Page 37: ...a sirkulasi udara di dalam ruangan baik Tidak boleh ada sumber panas atau uap di dekat unit Dimensi H yang sesuai diperlukan untuk mendapatkan kemiringan untuk pembuangan seperti yang ditunjukkan pada gambar Konfirmasi hubungan posisi antara unit dan baut suspensi Pemasangan bukaan langit langit untuk membersihkan filter atau menyervis di bawah produk Tampilan dari atas Satuan mm inci Tampilan sam...

Page 38: ...lubang pembuangan seperti pada gambar untuk pembuangan air yang mudah Posisi baut Konsol Tempat di mana unit dapat dipasang dalam posisi rata dan dapat mendukung berat unit Tempat di mana unit dapat menahan getarannya Tempat di mana servis dapat dilakukan dengan mudah KASUS 2 Dimensi Kapasitas kBtu h A B C D E F G H I J 9 733 772 628 700 36 190 20 660 155 700 12 18 933 972 628 700 36 190 20 860 15...

Page 39: ... ke atas baut suspensi untuk mengunci baut suspensi pada langit langit Pasang baut suspensi pada set anchor dengan kencang Pasang pelat pemasangan pada baut suspensi sesuaikan ketinggian kira kira menggunakan mur ring dan ring pegas 1 Set anchor Bangunan lama Bangunan baru 2 Ring pelat 3 Ring pegas 4 Mur 5 Baut suspensi PERHATIAN Kabel daya yang terhubung ke unit harus dipilih sesuai dengan spesif...

Page 40: ...kuran pengisapan dari bawah tekuk belakang Panel dan sekrup dengan kotak kabinet Outlet udara Filter Udara Belakang Panel Outlet udara Filter Udara Belakang Panel Outlet udara Filter Udara Belakang Panel Langit langit Langit langit 1 100 1 50 Lubang pembuangan BENAR SALAH Lubang pembuangan Perhatian untuk kemiringan unit dan pipa pembuangan Letakkan selang pembuangan miring ke bawah agar air akan ...

Page 41: ...k tidak membuat tekukan ke atas dan bawah untuk mencegah arus balik Selama sambungan pipa pembuangan berhati hatilah untuk tidak menggunakan tenaga yang berlebihan pada port pembuangan unit dalam ruangan Diameter luar sambungan pembuangan pada unit dalam ruangan adalah 32 mm Bahan pipa Pipa polivinil klorida VP 25 dan alat kelengkapan pipa Pastikan untuk membuat penyekat panas pada pipa pembuangan...

Page 42: ...n panas yang sangat baik di atas 120 C 2 Tindakan pencegahan dalam keadaan kelembapan tinggi Pendingin ruangan ini telah diuji sesuai dengan Kondisi Standar KS dengan Kabut dan dikonfirmasi bahwa tidak ada kerusakan apa pun Akan tetapi jika alat dioperasikan untuk jangka waktu yang lama di atmosfer berkelembapan tinggi suhu titik embun lebih dari 23 C tetesan air dapat terbentuk Dalam hal demikian...

Page 43: ...k reklamasi jika ada kotak reklamasi Pasang produk sedemikian rupa agar tidak ada celah dengan sisi dinding dan mencegah goyang setelah pemasangan Dapat mengatur kabel pengendali jarak jauh ke tiga arah Arah pengaturan permukaan reklamasi dinding atas kanan Jika mengatur kabel pengendali jarak jauh ke sisi atas dan kanan silakan atur setelah melepaskan galur pemandu kabel pengendali jarak jauh Lep...

Page 44: ...i hati untuk tidak merusak komponen dalam saat memisahkan Silakan sambungkan unit dalam ruangan dan pengendali jarak jauh menggunakan kabel penghubung Silakan gunakan kabel ekstensi jika jarak antara pengendali jarak jauh berkabel dan unit dalam ruangan lebih dari 10m Silakan cek apakah konektor tersambung secara normal Kabel penghubung Sisi Unit Dalam Ruangan PERHATIAN Saat memasang pengendali ja...

Page 45: ...a Jangan memasang pengendali jarak jauh di tempat yang dapat dipengaruhi oleh Draft atau titik mati di belakang pintu dan di sudut Udara panas atau dingin dari saluran Panas pancaran dari matahari atau alat Pipa dan cerobong yang tersembunyi Area yang tidak terkendali seperti dinding luar di belakang pengendali jarak jauh Pengendali jarak jauh ini dilengkapi dengan tampilan LED tujuh segmen Untuk ...

Page 46: ...suhu naik turun kontrol aliran angin arah angin tombol mulai berhenti 4 Jika tombol ditekan lama selama 3 detik alat akan masuk ke mode pengaturan pengendali jarak jauh Jika ditekan sesaat sekali alat masuk ke mode pengaturan pengguna Silakan tekan selama lebih dari 3 detik untuk pastinya Silakan batalkan arah angin kanan dan kiri untuk produk RAC 1 Angka pengaturan 01 berkedip pada bagian bawah j...

Page 47: ...tombol akan membuatnya keluar dari mode pengaturan Setelah pengaturan alat akan otomatis keluar dari mode pengaturan jika tidak ada masukan tombol selama 25 detik Saat keluar tanpa menekan tombol set nilai yang diubah tidak akan tercermin 7 Jika masuk ke mode pengaturan alamat dengan menggunakan tombol itu akan ditunjukkan seperti gambar di bawah ini 2 Jika tombol ditekan lama selama 3 detik alat ...

Page 48: ... akan membuatnya keluar dari mode pengaturan Setelah pengaturan alat akan otomatis keluar dari mode pengaturan jika tidak ada masukan tombol selama 25 detik Saat keluar tanpa menekan tombol set nilai yang diubah tidak akan tercermin Tabel Termistor Pemilihan sensor suhu Fungsi 01 Pengendali jarak jauh Operasi pada sensor suhu pengendali jarak jauh 02 Unit dalam ruangan Operasi pada sensor suhu uni...

Page 49: ... akan otomatis keluar dari mode pengaturan jika tidak ada masukan tombol selama 25 detik Saat keluar tanpa menekan tombol set nilai yang diubah tidak akan tercermin 1 Jika tombol ditekan berulang kali alat akan menuju ke menu pemilihan master slave seperti gambar di bawah ini 2 5 Lihat bagian kontrol kelompok untuk selengkapnya Saat mengontrol dalam kelompok pengaturan operasi dasar kekuatan alira...

Page 50: ...ntact pengendali jarak jauh seperti gambar di bawah ini 2 Menekan tombol akan membuatnya keluar dari mode pengaturan Setelah pengaturan alat akan otomatis keluar dari mode pengaturan jika tidak ada masukan tombol selama 25 detik Saat keluar tanpa menekan tombol set nilai yang diubah tidak akan tercermin 5 Pengaturan Pemasang Pengaturan Mode Kontak Kering Fungsi dry contact adalah fungsi yang hanya...

Page 51: ...ombol ditekan lama selama 3 detik alat akan masuk ke mode pengaturan pengendali jarak jauh Jika ditekan sesaat sekali alat masuk ke mode pengaturan pengguna Silakan tekan selama lebih dari 3 detik untuk pastinya 1 Tekan tombol untuk keluar atau sistem akan otomatis keluar setelah 25 detik tanpa masukan apa pun 5 Pilih mode satuan suhu dengan menekan tombol 00 Celsius 01 Fahrenheit 3 Tekan tombol u...

Page 52: ...tik alat akan masuk ke mode pengaturan pengendali jarak jauh Jika ditekan sesaat sekali alat masuk ke mode pengaturan pengguna Silakan tekan selama lebih dari 3 detik untuk pastinya 1 Jika tombol ditekan berulang kali alat akan menuju ke kode fungsi pilihan yang dipilih seperti gambar di bawah ini 2 Menekan tombol akan membuatnya keluar dari mode pengaturan Setelah pengaturan alat akan otomatis ke...

Page 53: ... Deskripsi 42 00 42 01 42 02 Tidak membatasi pengaturan mode operasi Pengguna dapat menyetel ke mode pendinginan saja Pengguna dapat menyetel ke mode pemanasan saja Akses ke kode pemasang nomor 42 di menu dengan menggunakan tombol 2 Pilih master slave pengendali jarak jauh dengan menggunakan tombol 3 Nilai kode untuk pengaturan kunci mode Nilai setelan h Ini hanya dapat membatasi tombol pengendali...

Page 54: ...kan tombol itu akan ditunjukkan seperti gambar di bawah ini 2 Pilih tingkat kipas ESP dengan menekan tombol 01 sangat rendah 02 rendah 03 sedang 04 tinggi 05 kuat 3 Akses ke pengaturan nilai ESP dengan menekan tombol Nilainya 000 saat dikirim dari gudang 4 Tekan tombol untuk mengatur nilai ESP Dimungkinkan untuk mengatur nilai ESP dari 1 sampai 255 di mana 1 adalah nilai terkecil dan 255 adalah ni...

Page 55: ...ia untuk rentang tertentu sesuai produk Tekan tombol untuk menyimpan 7 Pilih tingkat kipas ESP lagi dengan menggunakan tombol dan atur nilai ESP sebagai No 4 dan 5 yang sesuai dengan aliran angin 6 Tekan tombol untuk keluar Setelah pengaturan alat akan otomatis keluar dari mode pengaturan jika tidak ada masukan tombol selama 25 detik Saat keluar tanpa menekan tombol set nilai yang diubah tidak aka...

Page 56: ...bol dan tombol bersama sama selama lebih dari 3 detik setelah pengaturan selesai dilakukan mode pengaturan akan dilepaskan Jika tidak ada masukan tombol selama lebih dari 25 detik mode pengaturan pemasang juga akan dilepaskan 4 Saat menekan tombol dan tombol bersamaan selama lebih dari 3 detik sistem akan masuk ke mode pengaturan pemasang Setelah masuk ke mode pengaturan pemasang pilih kode pengat...

Page 57: ...109 117 HIGH 9 97 103 108 117 124 131 Model Tingkat CMM Tekanan Statis mmAq Pa 0 0 1 10 2 20 3 29 4 39 5 49 Nilai Pengaturan 32 01 32 02 32 03 32 04 32 05 32 06 AMNW12GL2A2 AMNQ12GL2A0 ABNQ12GL2A2 LOW 7 78 82 87 93 100 107 MID 8 5 87 91 94 100 108 116 HIGH 10 96 100 103 109 117 125 Model Tingkat CMM Tekanan Statis mmAq Pa 0 0 1 10 2 20 3 29 4 39 5 49 Nilai Pengaturan 32 01 32 02 32 03 32 04 32 05 ...

Page 58: ...yala Default SW3 Kontrol Kelompok Pemilihan Master atau Slave Master Slave Mati SW4 Mode Dry Contact Pemilihan Mode Dry Contact Pengendali jarak jauh berkabel nirkabel Pemilihan Mode pengoperasian Manual atau Otomatis Otomatis Mati SW5 Pemasangan Pengoperasian kipas terus menerus Penghapusan pengoperasian terus menerus Bekerja Mati ...

Page 59: ...29 BAHASA INDONESIA ...

Page 60: ...Diimpor oleh PT LG ELECTRONICS INDONESIA GANDARIA 8 OFFICE TOWER LT 29 BC 31 ABCD JL SULTAN ISKANDAR MUDA KEBAYORAN LAMA JAKATA SELATAN 12240 DKI JAKARTA RAYA INDONESIA ...

Reviews: