44 Multi type Air Conditioner
Installation
3. Art Cool Deluxe Type Indoor Unit
Connection of piping Indoor
• Preparing the indoor unit's piping and drain hose for
installation through the wall.
• Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
• Replace the plastic tubing holder in the original position.
(Optional)
1. Route the indoor tubing and the drain hose in the
direction of rear right.
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
4. Indoor unit installation
• Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the instal-
lation plate.) Ensure that the hooks are properly seat-
ed on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
4. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
• Align the center of the pipes and sufficiently tighten
the flare nut by hand.
• Tighten the flare nut with a wrench.
• When extending the drain hose at the indoor unit,
install the drain pipe.
For right rear piping
Drain hose
Connecting
cable
Indoor unit tubing
Flare nut
Pipes
Drain hose
Connecting
pipe
Connecting cable
Tape
Drain hose
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Summary of Contents for A2UQ166FA0
Page 135: ...Service Manual 135 Schematic Diagram 2 Art Cool Type ...
Page 136: ...136 Multi type Air Conditioner Schematic Diagram 3 Art Cool Deluxe Type ...
Page 148: ...148 Multi type Air Conditioner Schematic Diagram 2 Art Cool Type TOP VIEW BOTTOM VIEW ...
Page 151: ...Service Manual 151 Schematic Diagram Low static BT BT1 chassis ...
Page 152: ...152 Multi type Air Conditioner Schematic Diagram 5 Casset Type 1 way TC chasis ...
Page 153: ...Service Manual 153 Schematic Diagram 4 way TE TF TD chasis 58 B ...
Page 155: ...Service Manual 155 Schematic Diagram VB chassis ...
Page 158: ...158 Multi type Air Conditioner Schematic Diagram 3 Outdoor Unit 1 Component side ...
Page 159: ...Service Manual 159 Schematic Diagram 2 Solder side ...
Page 238: ...P No 3828A22009C October 2006 Printed in Korea ...