Service Manual 189
12) Troubleshooting CH51, CH60
51
60
Over capacity
EEPROM
Check sum
• Over capacity
Combination
• Check sum error
• Check the indoor unit capacity.
• Check the combination table.
• Check the PCB ASM P/No.
• Check the poor soldering.
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
• CH 51
1. Check the indoor unit capacity.
• CH 60
1. Check the insertion condition of EEPROM.
2. Check the poor soldering
Troubleshooting Guide
Model
Gross max. capacity
Max. single indoor unit capacity
A2UW146FA0
21k
12k
A2UW186FA0
24k
12K
A3UW186FA0
A3UW246FA0
33k
18K
A4UW246FA0
A4UW306FA0
39k
18K
A6UW406FA0
52k
24K