Service Manual 175
Troubleshooting Guide
General Information
■
Error Indicator (Indoor)
• The function is to self-diagnosis air conditioner and express the troubles if there is any trouble.
• Error mark is displayed on display window of indoor units and wired-remote controller, and LED of outdoor unit
control board.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurs, if error is released, error LED is also released simultaneously.
■
Indoor Error
1 digit
10 digit
Case of error
Contents
Error
code
Open / Short
Outlet pipe sensor
06
Different operation mode
Different operation mode
07
Communication Poorly
Float switch Open
Communication Poorly
Open / Short
Open / Short
Air sensor (open/short)
01
Inlet pipe sensor
02
Communication(Indoor
↔
Wired R/Control)
03
Drain pump/ Float switch
04
Communication(Indoor
↔
Outdoor)
05
Off
Off
Off
Off
Off
Off
Off
Indoor
Status
Summary of Contents for A2UQ166FA0
Page 135: ...Service Manual 135 Schematic Diagram 2 Art Cool Type ...
Page 136: ...136 Multi type Air Conditioner Schematic Diagram 3 Art Cool Deluxe Type ...
Page 148: ...148 Multi type Air Conditioner Schematic Diagram 2 Art Cool Type TOP VIEW BOTTOM VIEW ...
Page 151: ...Service Manual 151 Schematic Diagram Low static BT BT1 chassis ...
Page 152: ...152 Multi type Air Conditioner Schematic Diagram 5 Casset Type 1 way TC chasis ...
Page 153: ...Service Manual 153 Schematic Diagram 4 way TE TF TD chasis 58 B ...
Page 155: ...Service Manual 155 Schematic Diagram VB chassis ...
Page 158: ...158 Multi type Air Conditioner Schematic Diagram 3 Outdoor Unit 1 Component side ...
Page 159: ...Service Manual 159 Schematic Diagram 2 Solder side ...
Page 238: ...P No 3828A22009C October 2006 Printed in Korea ...