Service Manual 171
Troubleshooting Guide
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)
Caused by the remote controller.
Caused by other parts except
the remote controller
When the mark ( ) is displayed in LCD
screen, replace battery.
Check the contact of CN-DISP 1 connector
When the detect switch (double key) inside the
remote controller door is fault, it is impossible to
operate temperature regulating(
▲
/
▼
) and wind
speed selecting.
Check DISP PWB Ass'y
-Voltage between CN1
➀
-
➆
: DC +5V
Check the Display PWB Ass'y
• Check receiver ass'y
Product doesn't operate with the remote controller.
Trouble 2
Summary of Contents for A2UQ166FA0
Page 135: ...Service Manual 135 Schematic Diagram 2 Art Cool Type ...
Page 136: ...136 Multi type Air Conditioner Schematic Diagram 3 Art Cool Deluxe Type ...
Page 148: ...148 Multi type Air Conditioner Schematic Diagram 2 Art Cool Type TOP VIEW BOTTOM VIEW ...
Page 151: ...Service Manual 151 Schematic Diagram Low static BT BT1 chassis ...
Page 152: ...152 Multi type Air Conditioner Schematic Diagram 5 Casset Type 1 way TC chasis ...
Page 153: ...Service Manual 153 Schematic Diagram 4 way TE TF TD chasis 58 B ...
Page 155: ...Service Manual 155 Schematic Diagram VB chassis ...
Page 158: ...158 Multi type Air Conditioner Schematic Diagram 3 Outdoor Unit 1 Component side ...
Page 159: ...Service Manual 159 Schematic Diagram 2 Solder side ...
Page 238: ...P No 3828A22009C October 2006 Printed in Korea ...