14
GA 01.600/10.02 - 07/01
Operation
Fig. 5 Wiring diagram for the TRIVAC E pumps with three-phase motor
Delta circuit
Star circuit
Voltage ranges for
Max. current consumption
Min. current
Setting for the
the three-phase
at an intake pressure of
consumption at
motor protection
motors
about 300 mbar
ultimate pressure
switch (motor data)
D
50 Hz
200 V - 240 V
2.2 A - 2.6 A
1.6 A - 2.5 A
2.8 A
60 Hz
200 V - 266 V
2.5 A - 2.3 A
1.4 A - 1.9 A
2.8 A
Y
50 Hz
346 V - 415 V
1.2 A - 1.5 A
0.9 A - 1.4 A
1.6 A
60 Hz
346 V - 460 V
1.4 A - 1.35 A
0.8 A - 1.2 A
1.6 A
D
50 Hz
200 V - 240 V
3 A - 3.8 A
2 A - 3.3 A
4 A
60 Hz
200 V - 277 V
3.3 A - 3.5 A
1.8 A - 3.1 A
3.6 A
Y
50 Hz
346 V - 415 V
1.8 A - 2.1 A
1 A - 1.5 A
2.3 A
60 Hz
346 V - 480 V
1.95 A - 2 A
0.95 A - 1.45 A
2.1 A
TRIVAC D 5 / 10 E
TRIVAC D 16 E
2.3.2.1 Current Drawn by the Three-Phase Motors of the TRIVAC D 5 E - D 16 E
Summary of Contents for D10E
Page 1: ......
Page 33: ...GA 01 600 10 02 07 01 33 ...