Example Regen Resistor Power Dissipation Calculation, continued
Example Step 8
Compare the ratings as follows:
Internal Regen resistor ratings of the MHDA1028
/
00:
P
pulse
= 21 kW
P
continuous
= 200W
Deceleration 1: P
pulse
= 940W < 21 kW rating
Deceleration 2: P
pulse
= 1258W < 21 kW rating
P
continuous
= 231W > 200W
Requires an external Regen resistor be used. Select the 250W external
Regen resistor or modify the profile to reduce the continuous power
dissipated.