Chapter 5 System Operation
94
890 USE 120 00
Procedure for Verifying System Operation, continued
Quick Tuning
Procedure,
continued
Note: The hardware enable is powered up upon detection of state sence versus
transition sensitivity.
Continued on next page
Step
Activity
7
Check safety devices such as hardware limit switches, emergency stop
circuitry and so forth.
WARNING!
MECHANICAL MOVEMENT HAZARD
Ensure personnel, tools and all other obstructions are clear of the
equipment.
Failure to observe this precaution can result in severe injury or
equipment damage.
8
Apply 0V to the analog command input on connector X3, terminals 4 and 5
or 6 and 7.
9
Turn on the AC mains power supply, drive being disabled.
10
Enable 24 Vdc on connector X3, terminal 15. Observe that 500 ms after
the power supply was switched on, the servo motor is motionless with a
standstill torque of M
0
.
11
Using the UniLink Oscilloscope Service Function, program a small 50-rpm
velocity command. If the servo motor oscillates, the Kp parameter in the
"speed controller" menu page must be adjusted.
Note: The Kp parameter may have to be adjusted after connecting the
load. Refer to UniLink on-line help for more tuning information.
Summary of Contents for MHDA1004
Page 1: ...Version 2 0 June 2003 31001643_K01_000_04 Lexium Servo Drive 17D Series User Guide...
Page 2: ......
Page 4: ...Preface iv 890 USE 120 00...
Page 14: ...Contents xiv 890 USE 120 00...
Page 28: ...14...
Page 46: ...32...
Page 56: ...42...
Page 112: ...Chapter 5 System Operation 98 890 USE 120 00...
Page 130: ...116 Continued on next page...
Page 148: ...134...
Page 172: ...158...
Page 198: ...184...
Page 204: ...Index 190 890 USE 120 00...