Leviton UPB 39A00-3 Installation Instructions And User Manual Download Page 1

LEVITON UPB™ THREE-PHASE REPEATER

Cat. No. 39A00-3

Installation Instructions and User’s Guide

INSTALLATION

ENGLISH

DI-021-HL393-05A

AR2243

(39I00-3)

DESCRIPTION

The Leviton UPB™ Three-Phase Repeater (TPR) is a small electronic device that enables communication between devices using the Universal Powerline Bus (UPB™) method 

of communication (such as HLC devices) on a three-phase 120/208VAC delta-wye, 60Hz powerline. The main purpose of the TPR is to transfer UPB™ multi-packet messages 

transmitted on one phase (leg) of the electrical system and strongly repeating them on to the other phases (legs) to ensure proper communication.
UPB™ communication was designed to work on a single phase powerline. In a three-phase environment, the signals will not directly jump across all three phases of a 120/208V 

electrical system. The TPR is designed to take any UPB™ multi-packet generated signal on a single phase and repeat them onto all three phases of the powerline.

INSTALLATION INSTRUCTIONS

 

1.  TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!
2.  Install the TPR into a suitable junction box or equivalent enclosure.
3.  Run wires from a three-pole circuit breaker to the workbox for Phase A, Phase B, Phase C, and Neutral (see illustration).
4.  Use wire nuts to connect the black wire of the TPR to Phase A, and the red wire to Phase B, and the blue wire to Phase C. Connect the white wire of the TPR to Neutral. Check 

that there are no bare wires protruding and cover the wire nuts with insulating tape if necessary.

5.  Check all wiring and connections, and turn on the main breaker.
6.  All three status LED indicators will light up if all of the connections are proper.

WARNINGS AND CAUTIONS

• 

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and 

test that power is off before wiring!

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.

•  If you are unsure about any part of these instructions, consult an electrician.

WARNINGS AND CAUTIONS

•  This product must be installed in a suitable junction box or equivalent enclosure.

•  Use this device with 

copper or copper-clad wire only.

•  For indoor use only.

•  SAVE THESE INSTRUCTIONS.

CONFIGURATION

Although the TPR will operate without any configuration, Leviton recommends that you use the UPB™ UPStart configuration software to add the TPR to the UPB network with a 

Unit ID.  Once added to the network, UPStart can then be used to adjust the receive sensitivity of the TPR and perform communication tests between other devices to insure proper 

system signal strength.
Adding the TPR to the UPStart Network
The TPR is added in to a network just like most other UPB™ devices. 

Select Device          Add Device

, place the TPR into Setup Mode, and then click the 

Next button. To place 

the TPR into Setup Mode, press the Program Button 5 times. To exit Setup Mode, press the Program Button twice.  While in Setup Mode, the LED indicators will blink blue. Once the 

TPR is added to the network, it may be assigned a Room and Device Name that is used for identification purposes.
Performing Communication Tests

It is important that the communication of your UPB™ network be tested to insure proper system signal strength. UPStart has a Repeater Communication Test that will test how well

each device communicates with the TPR and how well the TPR communicates with all devices. The Repeater Communication Test will show a record of the signal strength, noise 

level, and phase at all devices.

LEVITON UPB™ THREE-PHASE REPEATER WIRING DIAGRAM

Programming

Button

Status LED

3-Pole Circuit Breaker

Circuit Breaker Panel

Three Phase Electrical System

N

A

B

C

Neutral

White

Black

Red

Blue

Three Phase Repeater

WEB 

VERSION

Reviews: