background image

ENGLISH

SPECIFICATIONS

•  Suitable as Motor Disconnect on a circuit capable of delivering not more than 10,000 rms symmetrical 

amperes, 600 VAC maximum, when protected by a 30A time delay fuse.

•  Select conductor size in accordance with N.E.C. Table 310-16 or Canadien Electrical Code Table 2.
•  When equipment is installed in an enclosure, the enclosure size shall be in accordance with N.E.C. and 

appropriate electrical codes.

•  Overcurrent protection must not exceed the ampere rating of the controller.

TO INSTALL

WARNING:

 TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE ELECTRICAL 

CODES AND REGULATIONS.

WARNING:

 IF yOU ARE NOT SURE ABOUT ANy PART OF THESE INSTRUCTIONS, CONSULT A 

qUALIFIED ELECTRICIAN.

WARNING:

 

TO AVOID FIRE SHOCK, OR DEATH; 

TURN OFF POWER

 AT CIRCUIT BREAKER OR FUSE 

AND TEST THAT THE POWER IS OFF BEFORE INSTALLING.

CAUTION:

 

USE THIS DEVICE ONLy WITH COPPER WIRE.

1.  TURN OFF POWER.
2a. To Side Wire: 

Remove approx. 3/4" (1.9 cm) of insulation. Connect wires per appropriate WIRING 

DIAGRAM as follows: Loop wires clockwise 3/4 turn around terminal screws. Firmly tighten screws over 

wire loops. Torque terminal screws to 20 in.-lbs (2.3 N m).

2b. To Back Wire: 

 Remove approx. 1/2" (1.3 cm) of insulation per strip gage on device. Insert wires into wire 

ways next to appropriate terminal screws. Torque terminal screws to 20 in.-lbs (2.3 N m).

3. 

Side and back wire terminal screws accept up to #10 AWG copper wire.

 

NOTE: 

For #8 AWG wire, remove terminal clamp and use ring terminal 

(see Table 1)

.

4.

  MAKE SURE THERE ARE NO STRAy STRANDS OF WIRE AFTER INSTALLATION.

5. 

  Mount device using long mounting screws provided. Attach cover.

6. 

Restore power at circuit breaker or fuse. 

INSTALLATION IS COmPLETE.

manual motor Controllers

2-Pole, 1Ø General Purpose

Suitable as Motor Disconnect

Cat. Nos.: 

MS302 - 30A-600VAC 

MS402 - 40A-600VAC

3-Pole, 3Ø General Purpose

Suitable as Motor Disconnect 

Cat. Nos.: 

MS303 - 30A-600VAC 

MS403 - 40A-600VAC

INSTALLATION INSTRUCTIONS

Controles de motor manual

Propósito General 1Ø, 2-Polos,

Apropiado para desconectar motores 

Nos. de Cat. 

MS302 - 30A-600 VCA 

MS402 - 40A-600 VCA

Propósito General 3Ø, 3-Polos,

Apropiado para desconectar motores

Nos. de Cat. 

MS303 - 30A-600 VCA 

MS403 - 40A-600 VCA

INSTRUCCIONES dE INSTALACIóN

Commandes de moteur manuelles

Bipolaires, d’usage général (1 Ø)

Peuvent servir de sectionneurs.

Nos de cat. : 

MS302 - 30 A, 600 V c.a. 

MS402 - 40 A, 600 V c.a.

Tripolaires, d’usage général (3 Ø) 

Peuvent servir de sectionneurs.

Nos de cat. : 

MS303 - 30 A, 600 V c.a. 

MS403 - 40 A, 600 V c.a.

dIRECTIvES d’INSTALLATION

For Technical Assistance Call:

1-800-824-3005 (U.S.A. Only)

www.leviton.com

LImITEd 10 YEAR WARRANTY ANd EXCLUSIONS

Leviton  warrants  to  the  original  consumer  purchaser  and  not 

for the benefit of anyone else that this product at the time of its 

sale  by  Leviton  is  free  of  defects  in  materials  and  workmanship 

under  normal  and  proper  use  for  ten  years  from  the  purchase 

date. Leviton’s only obligation is to correct such defects by repair 

or  replacement,  at  its  option,  if  within  such  ten  year  period  the 

product  is  returned  prepaid,  with  proof  of  purchase  date,  and  a 

description  of  the  problem  to 

Leviton  manufacturing  Co.,  Inc., 

Att: Quality Assurance department, 59-25 Little Neck Parkway, 

Little Neck, New York 11362-2591.

 This warranty excludes and 

there  is  disclaimed  liability  for  labor  for  removal  of  this  product 

or  reinstallation.  This  warranty  is  void  if  this  product  is  installed 

improperly or in an improper environment, overloaded, misused, 

opened, abused, or altered in any manner, or is not used under 

normal operating conditions or not in accordance with any labels 

or instructions. 

There are no other or implied warranties of any 

kind,  including  merchantability  and  fitness  for  a  particular 

purpose

, but if any implied warranty is required by the applicable 

jurisdiction,  the  duration  of  any  such  implied  warranty,  including 

merchantability  and  fitness  for  a  particular  purpose,  is  limited  to 

ten years. 

Leviton is not liable for incidental, indirect, special, 

or  consequential  damages,  including  without  limitation, 

damage  to,  or  loss  of  use  of,  any  equipment,  lost  sales  or 

profits or delay or failure to perform this warranty obligation

The remedies provided herein are the exclusive remedies under 

this  warranty,  whether  based  on  contract,  tort  or  otherwise.

PK-93464-10-02-0A

Fig. 1 – Cat. Nos./

N

os

 de cat.

/

Nos. Cat.

 mS302 & mS402

motor

Moteur

L1

T1

T2

L2

OFF

Line/

Ligne/

Línea

600v AC/

c.a./

CA

,

 30A

600v AC/

c.a./

CA

,

 40A

L1

T1

T3

T2

L3

L2

Line/

Ligne/

Línea

 3

Line/

Ligne/

Línea

 2

Line/

Ligne/

Línea

 1

OFF

Fig. 2 – Cat. Nos./

N

os

 de cat.

/

Nos. Cat.

 mS303 & mS403

motor

Moteur

Line/

Ligne/

Línea

600v AC/

c.a./

CA

,

 30A

600v AC/

c.a./

CA

,

 40A

Table 1/

Tableau 1/

Tabla 1

 – Ring Terminals/Rondelles de câblage/Anillos Terminales

manufacturer Brand

Marque du abricant

Nombre del Fabricante

Hoffman Products

Hoffman Products

AMP

manufacturer Part Number

N

o

 du fabricant

No. de Parte de Fabricante

8-NK5R1

FN8-S5R1

323197

Leviton Cat. No.

N

o

 de cat. de Leviton

Leviton No. de Cat.

mS302

mS303

mS402

mS403

Table 2/

Tableau 2/

Tabla 2

 – maximum H.P./

Puissance maximale/

Máximo H.P.

mS302/mS402 (2 Poles, 1Ø)

MS302/MS402 (bipolaire, 1Ø)

MS302/MS402 (2 polos, 1Ø)

2

5

10

15

mS303/mS403 (3 Poles, 3Ø)

MS302/MS402 (tripolaire, 3Ø)

MS302/MS402 (3 polos, 3Ø)

3

7.5 (7,5)

15

20

volts / A.C.

Volts c.a.

Voltios/C.A.

120

240

480

600

2008 © Leviton mfg. Co., Inc.